Capillary / Temperature Probe / Sheath; General; Approved Process Connections - JUMO ATH.-SE Series Operating Manual

Surface-mounting thermostats
Hide thumbs Also See for ATH.-SE Series:
Table of Contents

Advertisement

3.4

Capillary / temperature probe / sheath

3.4.1 General

A
H

3.4.2 Approved process connections

Temperature
probe
Sheaths
H
Cutting through or kinking the capillary will lead to permanent failure of the
instrument!
Minimum permissible bending radius of the capillary is 5 mm.
The temperature probe must be fitted in a JUMO sheath, otherwise the
approval of the surface-mounting thermostat becomes invalid.
The temperature probe must be completely submerged in the medium.
In order to ensure the general accuracy of response, the instruments must only
be used with the sheaths supplied from the factory (diameter D = 8, 10 mm).
Only probes with a diameter d = 8 mm may be fitted in sheaths with a diameter
D = 10 mm.
When the operating medium is air, connection type "10" (without sheath) must
be selected.
10
20, 30
refer todata sheet 606710 !