Capillary/ Temperature Probe/ Pocket; General - JUMO EMf-80 Series Operating Instructions Manual

Panel-mounting thermostats
Hide thumbs Also See for EMf-80 Series:
Table of Contents

Advertisement

3 Mounting
3.3

Capillary/ temperature probe/ pocket

3.3.1 General

A
H
10
Cutting through or kinking the capillary will result in the permanent failure of
the instrument!
The minimum permissible bending radius of the capillary is 5 mm.
The temperature probe must be installed in JUMO pockets. If this is not the
case, the approval of the thermostat becomes void.
The temperature probe must be completely immersed in the medium.
Fitting several probes into a common pocket is permitted only with 2 or 3 plain
probes 6 mm dia. and pockets 15 x 0.75 mm.
When fitting 2 probes, the spring clip supplied by the factory must be fitted in
the pocket.
For use in air, Form A (without pocket) has to be used.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Emf-80Emf-80/uEmf-80/au

Table of Contents