Monitoring Functions Of The Cpu 410-5H - Siemens SIMATIC PCS 7 System Manual

Process control system cpu 410-5h process automation/cpu 410 smart
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

3.2

Monitoring functions of the CPU 410-5H

Monitoring functions and error messages
The hardware of the CPU and operating system provide monitoring functions to ensure
proper operation and defined reactions to errors. Various errors may also trigger a reaction
in the user program.
The table below provides an overview of possible errors and their causes, and the
corresponding responses of the CPU.
Additional test and information functions are available in each CPU; they can be initiated in
STEP 7.
Type of error
Access error
Time error
Power supply module(s)
fault (not power failure)
Diagnostic interrupt
Swapping interrupt
Redundancy error
CPU hardware fault
Program execution error
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 09/2014, A5E32631667-AB
Cause of error
Module failure (SM, FM, CP)
The user program execution time (OB 1 and all interrupts and
error OBs) exceeds the specified maximum cycle time.
OB request error
Overflow of the start information buffer
Time-of-day error interrupt
In the central or S7-400 expansion rack
at least one backup battery of the power supply module is com-
pletely discharged.
the backup battery voltage is missing.
the 24 V supply to the power supply module has failed.
An I/O module with interrupt capability reports a diagnostic interrupt
The synchronization module signals a diagnostic interrupt; see
Chapter Synchronization modules for the CPU 410-5H (Page 189)
The LED EXTF lights up with the first incoming diagnostic interrupt
and goes out with the outgoing diagnostic interrupt.
Removal or insertion of an SM, and insertion of a wrong module
type.
Removing a synchronization module.
Loss of redundancy on the CPUs
Redundancy loss/ station failure of a switched DP station
Failure of a DP master
Disconnecting the PN cable of a system-redundant PN network
Failure of a system-redundant device
A memory error was detected and eliminated
Priority class is called, but the corresponding OB is not availa-
ble.
In the case of an SFB call: Missing or faulty instance DB
Process image update error
Structure of the CPU 410-5H
3.2 Monitoring functions of the CPU 410-5H
Error LED
EXTF
INTF
EXTF
EXTF
EXTF
REDF
INTF
INTF
EXTF
37