Block
FB 452 RED_DIAG
FB 453 RED_STATUS
Note
These are guide values, not absolute values. The actual value may deviate from these
specifications in some cases. This overview is intended as a guide and should help you
estimate how use of the Redundant IO CGP V52 library may change the cycle time.
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 09/2014, A5E32631667-AB
Runtime in stand-alone/single mode
Called in OB 72: 160 µs
Called in OB 82, 83, 85:
250 µs + 5 µs / configured module pairs
Under extreme conditions the runtime of FB
RED_DIAG is increased up to 1.5 ms. .
This is the case when the working DB is 60
KB or larger and if there are interrupt trigger
addresses that do not belong to the redun-
dant I/O.
160 μs 4 μs/ configured module pairs * num-
ber of module pairs)
The runtime depends on the random position
of the module being searched for in the work-
ing DB.
When a module address is not redundant, the
entire working DB is searched. This results in
the longest runtime of FB RED_STATUS.
The number of module pairs is based either
on all inputs (DI/AI) or all outputs (DO/AO).
16.16 Runtimes of the FCs and FBs for redundant I/Os
Runtime in redundant mode
Called in OB 72: 360 µs
Called in OB 82, 83, 85:
430 μs (basic load) + 6 μs / configured mod-
ule pairs
Under extreme conditions the runtime of FB
RED_DIAG is increased up to 1.5 ms. .
This is the case when the working DB is 60
KB or larger and if there are interrupt trigger
addresses that do not belong to the redun-
dant I/O.
350 μs + 5 μs / configured module pairs *
number of module pairs)
The runtime depends on the random position
of the module being searched for in the work-
ing DB.
When a module address is not redundant, the
entire working DB is searched. This results in
the longest runtime of FB RED_STATUS.
The number of module pairs is based either
on all inputs (DI/AI) or all outputs (DO/AO).
Supplementary information