Technical data
14.1 Technical specifications of the CPU 410-5H; (6ES7 410-5HX08-0AB0)
Integrated switch
Number of ports
Automatic determination of transmission rate
Autonegotiation
Autocrossing
Change of the IP address at runtime, supported
Number of connection resources
Media redundancy
Supported
Changeover time at line interruption, typ.
Number of nodes on the ring, max.
Functionality
PROFINET IO controller
PROFINET IO device
PROFINET CBA
Open IE communication
Web server
PROFINET IO controller
Transmission rate, max.
Number of connectable IO devices, max.
Number of connectable IO devices for RT, max.
of which in line, max.
Shared device, supported
Prioritized startup supported
Enabling/disabling of IO devices
Hot swapping of IO devices (partner ports), supported
Device replacement without removable medium
Send clocks
Update time
Services
PG/OP communication
S7 routing
S7 communication
Open IE communication
Address range
Inputs, max.
Outputs, max.
User data consistency, max.
Open IE communication
Open IE communication, supported
210
6ES7410-5HX08-0AB0
Yes
2
Yes; Autosensing
Yes
Yes
No
120
Yes
200 ms
50
Yes
No
No
Yes
No
100 Mbps
250
250
250
No; but can be used in S7 framework
No
No
No
Yes
250 µs, 500 µs, 1 ms, 2 ms, 4 ms
250 µs to 512 ms, minimum value depends on the amount
of configured user data and the configured operating mode
or redundancy mode
Yes
Yes
Yes
Yes
8 Kbyte; up to 3 800 IO (channels)
8 Kbyte; up to 3 800 IO (channels)
1024 bytes
Yes