Failure And Replacement Of A Profibus Dp Master - Siemens SIMATIC PCS 7 System Manual

Process control system cpu 410-5h process automation/cpu 410 smart
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Failure and replacement of components during redundant operation
11.2 Failure and replacement of components of the distributed I/Os
To replace signal and function modules of an S7-300, perform the following steps:
Step
What to do?
1
Disconnect the module from its load current supply.
2
Remove the failed module (in RUN mode).
3
Disconnect the front connector and wiring.
4
Plug the front connector into the new module.
5
Insert the new module.
11.2.1

Failure and replacement of a PROFIBUS DP master

Starting situation
Failure
The S7-400H is in redundant system mode and a
DP master module fails.
Procedure
Proceed as follows to replace a PROFIBUS DP master:
Step
1
2
3
182
What to do?
Turn off the power supply of the central
rack.
Unplug the Profibus DP cable of the affect-
ed DP master module.
Replace the module.
How does the system react?
Both CPUs generate a remove/insert
interrupt and enter the event in the diagnostic
buffer and the system status list.
-
-
Both CPUs generate a remove/insert
interrupt and enter the event in the diagnostic
buffer and the system status list.
Parameters are assigned automatically to the
module by the CPU concerned and the module is
addressed again.
How does the system react?
With single-channel one-sided I/O:
The DP master can no longer process con-
nected DP slaves.
With switched I/O:
DP slaves are addressed via the DP master
of the partner.
How does the system react?
The fault-tolerant system switches to single
mode.
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 09/2014, A5E32631667-AB