Properties And Technical Specifications Of Cpu 410 Smart; Cpu 410 Smart - Siemens SIMATIC PCS 7 System Manual

Process control system cpu 410-5h process automation/cpu 410 smart
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Properties and technical specifications of CPU 410
SMART
15.1

CPU 410 SMART

CPU 410-5H and CPU 410 SMART
Note
Except for the special features described in this section, the CPU 410 SMART behaves like
a CPU 410-5H. Taking this section into consideration, the statements made in this manual
about the CPU 410-5H also apply to the CPU 410 SMART.
PO configuration limits
You can only operate the CPU 410 SMART with the supplied System Expansion Card PO
800 for a maximum of 800 process objects. Operation with a different SEC is not possible.
An expansion of the PO configuration limits is not possible.
DP master interface
You cannot use external DP master interfaces with the CPU 410 SMART. Only the
integrated DP interface is available.
The CPU 410 SMART supports 48 devices at each of the two integrated PN/IO interfaces.
The number of slots is limited to 1536 at each integrated PN/IO interface.
The DP interface of the CPU 410 SMART supports 1536 byte inputs and 1536 byte outputs.
The address range is from 0 to 16 KB.
PN/IO controller
You cannot use an external IO controller with the CPU 410 SMART. Only the integrated
PN/IO interfaces are available.
The CPU 410 SMART supports 48 PNIO devices. The number of slots is limited to 1536.
The PN/IO interfaces of the CPU 410 SMART each support 1536 byte inputs and 1536 byte
outputs.
The address range is from 0 to 16 KB.
Fail-safe operation
You cannot use the CPU 410 SMART as fail-safe CPU. Fail-safe operation is not supported.
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 09/2014, A5E32631667-AB
15
215