Flueing options
For lowest cost, optimal performance, ease of installation and servicing, Rinnai
recommend short flue installations (less than 3 m) are considered before all other
options. Short flue installations are shown below.
ESWTERM
ESWTERM
The gas pressures of the Linear are factory set for short flue installations (less than 3 m).
Installations greater than 3 m are long flue installations and will require a dip switch change, refer
commissioning instructions.
When considering the location of the fire care must be taken to ensure the flue path is free from
obstructions such as studs, noggins, joist, braces, electrics etc.
6 | Linear flue installation guide 13541-A 01-20
ASPDFK
LSFEXTKIT01
45° bends
ESPIPE900
ESWTERM
45° bends
LSFKIT01