Side direct flue assembly

The direct flue (ASPDFK) is suitable for
walls up to 385 mm thick—can be cut to
size and the wall terminal reattached.
The flue must terminate 300 mm above
ground level.
With the Linear installed into the support framing:
1. Create the wall penetration. The minimum diameter required is 80 mm to non-combustible
surfaces such as brick, and 100 mm to combustible surfaces such as plaster. Allow for a
continuous 2° fall from the Linear to the wall terminal.
2. Slide the internal wall plate over the terminal end of the ASPDFK pipe until it is nested on the
raised ring of the flue transition.
3. Pass the ASPDFK through the internal wall penetration.
4. Make the Linear exhaust and combustion air hose connections, refer p.9.
5. Slide the internal wall plate so it is flush with the wall.
6. Create the wall terminal, refer p.17.
I n t
e r i
o r
w a
l l
12 | Linear flue installation guide 13541-A 01-20
Max. wall thickness 385 mm
Internal wall plate, outer face
ASPDFK
Flue exhaust
Air inlet pipe
E x
t e r
i o r
w a
l l
outlet