Valor AutoFire G4 Installation Manual page 10

Direct vent gas fireplace insert gas fireplace natural gas 785yn propane gas 785yp
Table of Contents

Advertisement

Clearances
Clearances to Sidewall
Sidewall Clearances
sidewall
9" (229 mm)
Minimum distance from side of appliance (liner box) to
combustible wall: 9" [229 mm] (see above).
Mantel legs projecting forward less than 6" [152 mm]
may be located within 5" [127 mm] of the side of the
appliance (liner box).
Floor/ Hearth Clearances
Combustible shims/supports may be used beneath
the appliance to level or raise the appliance within the
existing fi replace cavity.
Combustible fl ooring/hearths in front of the appliance
must be at a minimum of 4" [102 mm] below the
bottom of the appliance. The gas insert does not
require a hearth.
10