Basic Installation and Operation Guide
Caution!
Decel is THE OPPOSITE of braking. Enabling the Decel feature will make the motor take
LONGER to stop than if it were simply turned off.
44 |
P a g e
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
5.6.6

Restart Delay

The TE Series can be programmed to delay restarting upon restoration
of line power after an outage. This allows multiple units to be
programmed to restart at staggered times in an effort to avoid causing
additional problems with the power supply system. Another term for this
is "Sequential Start Delay".
F028 = Restart Delay Time
Factory Setting = 0 (Disabled)
Range = 0 = Disabled (no delay), or 1 - 999 seconds
Sets a delay time before the starter can be restarted after a
complete loss of power. Use this if multiple motors are
connected to a supply system that may have trouble providing
adequate power to restart them all at the same time. By using
different Restart Delay Times on each unit, a sequential restart
can be achieved.
Note:
This is similar to the Coast Down Lockout Timer in F048, however it
only activates on Power Loss.
F029 = Reserved