Remote Keypad Mounting - Toshiba TE Series Instruction Manual

Low voltage digital solid state soft starter 18 – 1250a
Hide thumbs Also See for TE Series:
Table of Contents

Advertisement

Basic Installation and Operation Guide
Model
Number
TE-18-BP
TE-28-BP
TE-39-BP
TE-48-BP
TE-62-BP
TE-78-BP
TE-92-BP
TE-112-BP
TE-150-BP
TE-160-BP
TE-210-BP
TE-275-BP
TE-361-BP
TE-450-BP
TE-550-BP
TE-600-BP
TE-862-BP
TE-900-BP
TE-1006-BP
TE-1250-BP
Remote Keypad Mounting Kit
9 |
P a g e
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
2.6.1
Power Terminals:
Connection points are bus tabs with pre-drilled holes (see below). Use
appropriate compression or mechanical lugs for termination to these bus
tabs.
Suggested wire sizes and tightening torques for factory-supplied
connectors for conductors rated for 75C are shown in the chart below.
Always consult local codes and industry standard practices for proper
wires sizes to accommodate voltage drop and ambient conditions.
Table 2.6: TE Series Wire Ranges and Torque Specifications
Suggested
Current Range
Wire Size
Min.- Max.
AWG
9 - 18
12
14 - 28
10
19 - 39
8
24 - 48
6
36 - 62
4
39 - 78
3
46 - 92
2
56 - 112
2
75 - 150
0
80 - 160
2/0
105 - 210
4/0
138 - 275
300 kCMIL
180 - 361
500 kCMIL
225 - 450
2 x 250 kCMIL
275 - 550
2 x 250 kCMIL
TBD
300 – 600
TBD
431 – 862
TBD
450 – 900
TBD
503 - 1006
625 - 1250
TBD
Note: TBD = To Be Determined at a later date.
2.7

Remote Keypad Mounting

The keypad / operator interface unit can be remotely mounted up to 10'
(3 meters) away from the starter, i.e. on the enclosure door. A remote
mounting kit is necessary, which consists of an adaptor plate, a
doorframe for NEMA 1 or NEMA 12 enclosures and a pre-assembled
ribbon cable available in 1-meter length increments. Detailed assembly
instructions and an enclosure cutout template are included with the kit.
See Product Selection Guide for part numbers of the available kits.
Figure 2.7
Components
Tightening
Screw / Bolt
Tightening
Torque
Size
in.-lbs.
1 x M5
35
(included)
1 x M8
45
(included)
1 x M8
80
(included)
1 x 0.38" hole
(M10)
for User
200
supplied
lugs
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
Type 12
Door Frame
Ribbon Cable,
1, 2 or 3 Meters
(3.28, 6.56 or 9.84')
TE Starter
Suggested
Torque
Wire Size
2
Nm
ISOmm
6
10
4
16
16
25
35
5
35
50
70
9
70
120
150
15
300
2 x 150
2 x 150
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
Adaptor Plate

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents