Toshiba TE Series Instruction Manual page 50

Low voltage digital solid state soft starter 18 – 1250a
Hide thumbs Also See for TE Series:
Table of Contents

Advertisement

Basic Installation and Operation Guide
Note: Jog functions may become disabled by Communications port function F068 setting 3.
See section 5.6.10 for details.
Jog Voltage
Voltage Ramp
Setting
Jog
Command
M ax.
New Start
Jog
Time
Command
Time
Figure 5.6.3.1:
Voltage Jog and Jog Time
Jog Current
Current Ramp
Setting
Jog
Command
New Start
Command
Time
Figure 5.6.3.2:
Current Jog
41 |
P a g e
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
5.6.3
Jog Mode
The Jog Function is another user optional feature and is controlled by
closing the input on TB1 Terminals 6 and 7. If this input is left open, the
TE Series will ignore all Jog settings. Engaging the Jog feature along
with the Start / Run Command provides an output from the SCRs, but will
not continue ramping to full acceleration. This feature can Jog the motor
at either a preset Voltage (F019 – F021) or a preset Current (F021)
depending upon the settings of the Ramp Type from F010, and can be
initiated along with Ramp 1 or Ramp 2 (see Dual Ramp Select, Section
4.2.5 and 5.6.2.a). It is also sometimes useful to use Jog in combination
with Ramp 2, see section 4.2.5.c.
Ramp 1 (Dual Ramp Input
Open)
Setting
Ramp &
Initial
from
Jog
Torque
F010
Type
from...
1
Voltage
F011
2
Current
F012
3
Voltage
F011
4
Current
F012
Table 5.6.3: Jog Settings
Caution:
Although the Thermal Register tracks all motor current use,
continuous usage of the Jog feature risks thermal motor damage or
nuisance tripping.
F019 = Voltage Jog
Factory Setting = 50%
Range = 5 - 100%
Sets the voltage level of the Jog feature and is typically used to
check rotation, alignment, or to slowly move a load into position.
Jogging at a set voltage has no current control so the duration of
the applied voltage must be limited to prevent excessive motor
heating.
F020 = Time of Voltage Jog
Factory Setting = 10 seconds
Range = 1 - 20 seconds
Set to minimize motor heating during a voltage jog. This setting
is the maximum allowable time for jogging the motor using
voltage only.
F021 = Current Jog
Factory Setting = 150%
Range = 100 - 500%
Sets output of a current Jog. The current jog feature is typically
used to check rotation, alignment, or slowly move a load into
position. This is not time-limited but should be used cautiously.
Ramp 2 (Dual Ramp Input
Closed)
Jog
Ramp &
Initial
Torque
Jog
Torque
from...
Type
from...
F019
Voltage
F015
F021
Current
F016
F019
Current
F016
F021
Voltage
F015
Jog
Torque
from...
F019
F021
F021
F019

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents