Program Mode - Toshiba TE Series Instruction Manual

Low voltage digital solid state soft starter 18 – 1250a
Hide thumbs Also See for TE Series:
Table of Contents

Advertisement

Basic Installation and Operation Guide
Example: Figure 5.4.1
Viewing a Function's Set Value:
Motor FLA Setting
[0000.] Indicates that Phase A is drawing no current
(unit is in Off mode).
Press the Fn key
[F001]
Indicates that this is Function 001 (Motor FLA).
Press Read / Enter key
to view the F001's value
[0306]
Indicates that the programmed motor FLA is
360 Amps.
Press the Fn key
to return to the function
[F001]
Indicates that you have returned to the Function
Select screen.
Press the Fn key again
to return to the Status Display Mode
[0000.] Default screen.
25 |
P a g e
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
5.4

Program Mode

The starter must be OFF in order to enter the Program Mode.
Use the Program Mode to view or change Function (Fn) settings. To
enter the Program Mode, press the [Fn] key once from the Status
Screen described in 5.3.1 above. The first time you enter the Program
Mode after power has been cycled to the starter, the initial function
[F001] should be displayed with the selected digit flashing. If the TE
Series starter has been programmed and power to the unit has not been
cycled, the readout will display the last function viewed or changed. To
change to a different function, use the arrow keys.
5.4.1 Viewing Function Programming and Values
The programming of each individual Function can be viewed without
making changes (values can also be viewed in the Run Mode; however,
no changes can be made). Each Function is signified by the letter "F" in
the beginning of the data, the 4 digit value of the function follows after
pushing the [READ/ENTER] key
[F001] "F" indicates the programmable Function.
[0000] This is the present setting of the applicable function. This
display may include decimals between digits depending on the function
setting's range and incremental steps.
Note:
If password protection has been enabled, the operator will need to
obtain password access before function settings can be changed.
See Section 5.6.11 and Appendix 3.
Display
M eans...
Shows...
Default Display:
0000.
Press
Phase A Current
Key...
Selecting
F001
Fn
Function #1
Fn 1 Value:
READ
0360
ENTER
FLA = 360A
Return to Function
F001
Fn
# Selection
Return to
0000.
Fn
Default Display
Without Change
Figure 5.4.1:
View ing a Function's Set Value