Basic Installation and Operation Guide
Appendix 5 (cont.) Soft Starter Settings Record
Fn #
Group
Function Description
Pump Flex Control /
F024
Deceleration Ramp
Begin Decel Level (BDL),
F025
Immediate Drop Down Torque
F026
Decel Shut Off Voltage
F027
Decel Ramp Time
Restart Delay Time
F028
(Sequential Start Delay)
Reserved for Factory Use
F029
79 |
P a g e
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
Adjustment / Display Range
0 = Disabled (coast to stop)
1 = Enabled, except after OL trip
2 = Enabled, continued Decel even
if there is an OL trip
0 - 100 % of Output Voltage
0 to (BDL minus 1)% Voltage
1 – 60 Seconds
0 = Disabled, or
1-999 seconds after a Power Loss
(Status can be read in F054)
Setting
Factory
Setting
Increments
Setting
0
1
Disabled
1%
60%
1%
30%
10
1 second
seconds
0
1 second
Disabled

Hide quick links: