8. Modbus register assignment of the ISOMETER®
Depending on the device condition, the information in the registers is the measured
value without alarm; the measured value with alarm 1; the measured value with alarm 2;
or only the device error.
Measured value
Register
Without alarm
Alarm 1
R
1000
F
to
Insulation fault (71)
Insulation fault (1)
1003
[no alarm]
[prewarning]
1004
to
---
1007
U
1008
n
to
Voltage (76)
Overvoltage
1011
[no alarm]
(78) [alarm]
C
1012
e
to
capacitance (82)
1015
[no alarm]
U
1016
L+e
to
Voltage (76)
Undervoltage
1019
[no alarm]
(77) [alarm]
U
1020
L-e
to
Voltage (76)
1023
[no alarm]
1024
Fault location in %
to
--- (1022)
1027
[no alarm]
1028
to
---
1031
Measured value
1032
update counter
to
--- (1022)
1035
[no alarm]
( ) = Channel description code (refer to
[ ] = Alarm type (refer to
chapter
8.1.2.2)
isoBAT425_D00308_04_M_XXEN/07.2020
Device error
Alarm 2
R
R
F
F
Connection earth
Insulation fault (1)
[alarm]
[Device error]
---
---
U
n
Connection to sys-
tem (101)
[Device error]
---
---
U
n
---
---
---
---
---
---
---
---
---
Device error (115)
[Device error]
chapter
8.2)
Modbus register assignment of the ISOMETER®
Register
Property
3000
3001
---
3002
(102)
3003
3004
---
3005
---
3006
3007
3008
---
3009
3010
---
3011
---
3012
3013
---
3014
---
3015
---
3016
Description
Format
RW
Reserved
---
Pre-alarm value resis-
RW
tance measurement
UINT 16
"R1"
RW
Reserved
---
Alarm value resis-
RW
tance measurement
UINT 16
"R2"
RW
Reserved
---
U
specified bat-
BattH
RW
UINT 16
tery value, upper limit
RW
Reserved
---
U
specified bat-
BattL
RW
UINT 16
tery value, lower limit
RW
Reserved
---
U
cross fault
CrossH
RW
UINT 16
upper limit
RW
Reserved
---
U
cross fault
CrossL
RW
UINT 16
lower limit
Memory function for
RW
alarm messages
UINT 16
(Fault memory) "M"
Operating mode of
RW
UINT 16
alarm relay 1 "r1"
Operating mode of
RW
UINT 16
alarm relay 2 "r2"
RW
Bus address "Adr"
UINT 16
RW
Baud rate "Adr 1"
UINT 16
Unit
Value range
---
---
R2 ... 5000
---
---
10 ... R1
---
---
U
... 500
V
BattL
---
---
3 ... U
V
BattH
---
---
U
... 500
V
CrossL
---
---
3 ... U
V
CrossH
0 = Inactive
---
1 = Active
0 = n.o.
---
1 = n.c.
0 = n.o.
---
1 = n.c.
---
0 / 3 ... 90
0 = BMS
1 = 1.2 k
2 = 2.4 k
3 = 4.8 k
---
4 = 9.6 k
5 = 19.2 k
6 = 38.4 k
7 = 57.6 k
8 = 115.2 k
25