2. Outputs - Two SPDT relays with contacts rated as follows:
Normally Open Contacts: 20 amp resistive or inductive at 120-277 Vac
Normally Closed Contacts: 10 amp resistive or inductive at 120-277 Vac
3. Wiring - Power input and relay contact terminals can accommodate 10-16 AWG
- Sensor/override input terminals can accommodate 14-22 AWG
4. Power Outage Carryover - The program and time of day are maintained during a power outage
for a minimum of 60 hours.
8
1 HP at 120 Vac
2 HP at 208-277 Vac
5 amp tungsten at 120-240 Vac
20 amp ballast at 120 Vac
10 amp ballast at 208-277 Vac
470 VA at 120-240 Vac
1/4 HP at 120 Vac
1/2 HP at 208-277 Vac
3 amp ballast at 120-277 Vac
275 VA at 120-240 Vac