• 2 User Defined Inputs - Each input can be independently defined as one of two override types, an
enable input or as one of four sensor types.
• ON With Off Delay Override Input - Provides a retriggerable override input that is assignable to
either or both outputs. The affected output(s) will be overridden ON with the closing of the input
and remain ON as long as the input is closed. When the input is opened, the output(s) will remain
ON for the length of the off delay. The off delay is programmable from 0 seconds to 23 hours, 59
minutes and 59 seconds. Closing the input during the off delay will retrigger the override.
• Toggle Type Override Input - Provides a toggle type override input that is assignable to either or
both outputs. Closing the input causes the affected output(s) to be toggled to the opposite state and
remain in that state until the occurrence of the next programmed event. An optional timed-on from 1
second to 23 hours, 59 minutes and 59 seconds can be programmed. Upon completion of this
timed-on, the affected output(s) will return to the programmed state unless toggled off.
• Enable Input - The enable input is assignable to either or both outputs. The enable input acts as a
switch which opens and closes in series with the output. When open, the loads will remain off.
When closed, the output(s) follow the scheduled events.
• Sensor Input - The inputs can be configured as one of four sensor types:
F = degrees Fahrenheit (-40 to 215)
C = degrees Celsius (-40 to 102)
L = light level (0 to 100)
U = undefined (0 to 255)
4