Memory Clear - Paragon EL71 General Instructions Manual

Single channel & two channel electronic time controls
Table of Contents

Advertisement

From the HOL header, the control will loop around to the TIME header. The OVER (override) mode
is only accessible from the RUN mode. The following is a detailed explanation of each mode.
In all modes use the NEXT key to advance to the next item to be programmed or reviewed and the
PREVIOUS key to go back to the previous item. Use the + and - keys to modify the current (flash-
ing) item.

Memory Clear

Indicates that the memory has been cleared. Use the NEXT key to begin programming.
After initial power-up or a reset, the control will be in MEM CLR (memory clear) mode.
This mode is only accessible once.
Toggle between MAINTAIN (maintained) or MOMENTARY (momentary) operation using
the +/- key. When configured for momentary, relay 1 will provide the ON pulse and relay 2
will provide the OFF pulse. An EL72 configured for momentary operation will become a
one channel control. Use the NEXT key to continue programming.
Toggle between 12 hour (AM/PM) or 24 hour (00:00-23:59) clock format using the +/- key.
NOTE: After selecting relay operation and clock format, press the PROGRAM key to
begin programming steps in the TIME header.