Specifications; Power-Dependent Specifications; Power, Currents And Enclosures - GE AF-600 FP Series Design And Installation Manual

Fan & pump drive
Hide thumbs Also See for AF-600 FP Series:
Table of Contents

Advertisement

Specifications

13 Specifications

13.1 Power-dependent Specifications

13.1.1 Power, Currents and Enclosures

HP
kW
A
1
0.75
4.6
2
1.5
7.5
3
2.2
10.6
5
3.7
16.7
7.5
5.5
24.2
10
7.5
30.8
15
11
46.2
20
15
59.4
25
18
74.8
30
22
88
40
30
115
50
37
143
60
45
170
Table 13.1 200-240 V
A
HP
kW
≤ 440 V
>440 V
1
0.75
2.4
2.12.7
2
1.5
4.1
3.4
3
2.2
5.6
4.8
5
4.0
10
8.2
7.5
5.5
13
11
10
7.5
16
14.5
15
11
24
21
20
15
32
27
25
18
37.5
34
30
22
44
40
40
30
61
52
50
37
73
65
60
45
90
80
75
55
106
105
100
75
147
130
125
90
177
160
150
110
212
190
200
132
260
240
250
160
315
302
300
200
395
361
350
250
480
443
TM
AF-600 FP
Design and Installation Guide
200-240 V
Input Efficiency
IP20/Chassis
5.9
0.96
6.8
0.96
9.5
0.96
Unit size 12
15
0.96
22
0.96
28
0.96
Unit size 23
42
0.96
54
0.96
Unit size 24
68
0.96
80
0.96
Unit size 33
104
0.96
130
0.96
Unit size 34
154
0.96
Input Efficiency
IP00/
Chassis
2.7
0.96
3.7
0.97
5
0.97
9
0.97
11.7
0.97
14.4
0.97
22
0.98
29
0.98
34
0.98
40
0.98
55
0.98
66
0.98
82
0.98
96
0.98
133
0.98
161
0.98
204
0.98
251
0.98
304
0.98
381
0.98
463
0.98
DET-768b
IP55/Type 12
Unit size 15
Unit size 21
Unit size 22
Unit size 31
Unit size 32
380-480 V
IP20/Chassis IP21/Type 1 IP54/IP55/Type 12 IP66/Type 4X
Unit size 12
Unit size 12
Unit size 13
Unit size 23
Unit size 24
Unit size 33
Unit size 34
Unit size 43h
Unit size 41h
Unit size 43h
Unit size 41h
Unit size 44h
Unit size 42h
IP66/Type 4X
Unit size 15
Unit size 21
Unit size 22
Unit size 31
Unit size 32
Unit size 15
Unit size 15
Unit size 15
Unit size 15
Unit size 21
Unit size 21
Unit size 22
Unit size 22
Unit size 31
Unit size 31
Unit size 32
Unit size 32
Unit size 41h
Unit size 41h
Unit size 42h
87
13
13

Advertisement

Table of Contents
loading