GE AF-600 FP Series Design And Installation Manual page 72

Fan & pump drive
Hide thumbs Also See for AF-600 FP Series:
Table of Contents

Advertisement

RS-485 Installation and Set...
Bit 04, Quick stop
Bit 04 = '0': Makes the motor speed decel to stop (set in
C-23 Quick Stop Decel Time).
Bit 04 = '1' leads to ramping.
Bit 05, Hold output frequency
Bit 05 = '0': The present output frequency (in Hz) freezes.
Change the frozen output frequency only by means of the
digital inputs (E-01 Terminal 18 Digital Input to
E-06 Terminal 33 Digital Input) programmed to Speed up
and Slow down.
NOTE
If Freeze output is active, the frequency converter can only
be stopped by the following:
Bit 03 Coasting stop
Bit 02 DC braking
Digital input (E-01 Terminal 18 Digital Input to
E-06 Terminal 33 Digital Input) programmed to DC
braking, Coasting stop, or Reset and coasting stop.
Bit 06, Ramp stop/start
Bit 06 = '0': Causes a stop and makes the motor speed
decel to stop via the selected decel parameter. Bit 06 = '1':
Permits the frequency converter to start the motor, if the
other starting conditions are met.
Bit 07, Reset Bit 07 = '0': No reset. Bit 07 = '1': Resets a trip.
Reset is activated on the signal's leading edge, i.e. when
changing from logic '0' to logic '1'.
Bit 08, Jog
Bit 08 = '1': The output frequency is determined by
C-21 Jog Speed [RPM].
Bit 09, Selection of ramp 1/2
Bit 09 = "0": Ramp 1 is active (F-07 Accel Time 1 to
F-08 Decel Time 1). Bit 09 = "1": Ramp 2 (E-10 Accel Time 2
to E-11 Decel Time 2) is active.
Bit 10, Data not valid/Data valid
Tell the frequency converter whether to use or ignore the
control word. Bit 10 = '0': The control word is ignored. Bit
10 = '1': The control word is used. This function is relevant
because the telegram always contains the control word,
regardless of the telegram type. Thus, you can turn off the
control word if you do not want to use it when updating
or reading parameters.
Bit 11, Relay 01
Bit 11 = "0": Relay not activated. Bit 11 = "1": Relay 01
activated provided that Control word bit 11 is chosen in
E-24 Function Relay.
TM
AF-600 FP
Design and Installation Guide
Bit 12, Relay 04
Bit 12 = "0": Relay 04 is not activated. Bit 12 = "1": Relay 04
is activated provided that Control word bit 12 is chosen in
E-24 Function Relay.
Bit 13/14, Selection of set-up
Use bits 13 and 14 to choose from the four menu set-ups
according to Table 9.6.
Set-up
Table 9.6 Four Menu Set-ups
The function is only possible when Multi Set-Ups is selected
in K-10 Active Set-up.
Bit 15 Reverse
Bit 15 = '0': No reversing. Bit 15 = '1': Reversing. In the
default setting, reversing is set to digital in O-54 Reversing
Select. Bit 15 causes reversing only when Ser. communi-
cation, Logic or or Logic and is selected.
DET-768b
Bit 14
1
0
2
0
3
1
4
1
Bit 13
0
1
0
1
9
9
69

Advertisement

Table of Contents
loading

Table of Contents