GE AF-600 FP Series Design And Installation Manual page 106

Fan & pump drive
Hide thumbs Also See for AF-600 FP Series:
Table of Contents

Advertisement

Specifications
Surroundings
Enclosure, frame size 4X and 5X
Enclosure, frame size 6X
Vibration test
Relative humidity
Aggressive environment (IEC 60068-2-43) H
Test method according to IEC 60068-2-43 H
- with derating
- with full output power, typical EFF2 motors
- at full continuous drive output current
1)
For more information on derating see the AF-600 FP, section on Special Conditions.
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
Derating for high altitude, see section on special conditions in the Design Guide
EMC standards, Emission
EMC standards, Immunity
See section on special conditions in the Design Guide!
Control card performance
Scan interval
Control card, USB serial communication
USB standard
USB plug
CAUTION
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from protection earth. Use only isolated laptop/PC as connection to the USB
connector on the frequency converter or an isolated USB cable/converter.
Protection and Features
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches a
predefined level. An overload temperature cannot be reset until the temperature of the heatsink is below the
values stated in the tables on the following pages (Guideline - these temperatures may vary for different power
sizes, Unit Sizes, enclosure ratings etc.).
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or too high.
The frequency converter is protected against earth faults on motor terminals U, V, W.
TM
AF-600 FP
Design and Installation Guide
5% - 95%(IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
S (10 days)
2
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
DET-768b
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
USB type B "device" plug
IP00, IP21, IP54
IP21, IP54
0.7 g
class kD
max. 55 °C
1)
max. 50 °C
1)
max. 45 °C
1)
0 °C
-10 °C
-25 to +65/70 °C
1000 m
3000 m
5 ms
1.1 (Full speed)
13
13
103