Warnings and Alarms
Remove power from the frequency converter and check
motor phase W.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short time
period. Let the unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication fault
The network on the communication option card is not
working.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the frequency converter is lost and SP-10 Line failure is NOT
set to [0] No Function. Check the fuses to the frequency
converter and mains supply to the unit.
ALARM 38, Internal fault
When an internal fault occurs, a code number defined in
Table 10.5 is displayed.
Troubleshooting
Cycle power
Check that the option is properly installed
Check for loose or missing wiring
It may be necessary to contact your GE supplier or service
department. Note the code number for further trouble-
shooting directions.
No.
Text
0
Serial port cannot be restore. Contact your GE
supplier or GE Service Department.
256-258
Power EEPROM data is defective or too old.
0
10
Replace power card.
512-519
Internal fault. Contact your GE supplier or GE
Service Department.
783
Parameter value outside of min/max limits
1024-1284
Internal fault. Contact your GE supplier or the GE
Service Department.
1299
Option SW in slot A is too old
1300
Option SW in slot B is too old
1315
Option SW in slot A is not supported (not allowed)
1316
Option SW in slot B is not supported (not allowed)
1379-2819
Internal fault. Contact your GE supplier or GE
Service Department.
2561
Replace control card
2820
Keypad stack overflow
2821
Serial port overflow
2822
USB port overflow
3072-5122
Parameter value is outside its limits
5123
Option in slot A: Hardware incompatible with
control board hardware
5124
Option in slot B: Hardware incompatible with
control board hardware
5376-6231
Internal fault. Contact your GE supplier or GE
Service Department.
Table 10.5 Internal Fault Codes
80
TM
AF-600 FP
Design and Installation Guide
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove short-
circuit connection. Check E-00 Digital I/O Mode and
E-51 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove short-
circuit connection. Check E-00 Digital I/O Mode and
E-52 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For X30/6, check the load connected to X30/6 or remove
the short-circuit connection. Check E-56 Term X30/6 Digi
Out (OPCGPIO).
For X30/7, check the load connected to X30/7 or remove
the short-circuit connection. Check E-57 Term X30/7 Digi
Out (OPCGPIO).
ALARM 45, Earth fault 2
Earth (ground) fault on start-up.
Troubleshooting
ALARM 46, Power card supply
The supply on the power card is out of range.
There are three power supplies generated by the switch
mode power supply (SMPS) on the power card: 24 V, 5 V,
±18 V. When powered with three phase mains voltage, all
three supplies are monitored.
Troubleshooting
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. The external
24 V DC back-up power supply may be overloaded,
otherwise contact the GE supplier.
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
allowable limits. The power supply is measured on the
control card. Check for a defective control card. If an
option card is present, check for an overvoltage condition.
DET-768b
Check for proper earthing (grounding) and loose
connections.
Check for proper wire size.
Check motor cables for short-circuits or leakage
currents.
Check for a defective power card.
Check for a defective control card.
Check for a defective option card.
If a 24 V DC power supply is used, verify proper
supply power.