Fuse Specifications - GE AF-600 FP Series Design And Installation Manual

Fan & pump drive
Hide thumbs Also See for AF-600 FP Series:
Table of Contents

Advertisement

Specifications

13.3.4 Fuse Specifications

AF-600 3-
Recommended fuse
phase
size
[kW]/[HP]
0.75/1
1.5/2
gG-16
2.2/3
3.7/5
gG-20
5.5/7.5
7.5/10
gG-50
11/15
15/20
gG-80
18.5/25
22/30
gG-125
30/40
aR-160
37/50
aR-200
45/60
aR-250
Table 13.5 200-240 V, IP20/Open Chassis
AF-600 3-
Recommended fuse
phase
size
[kW]/[HP]
0.75/1
1.5/2
gG-20
2.2/3
3.7/5
5.5/7.5
7.5/10
gG-63
11/15
15/20
gG-80
18.5/25
gG-125
22/30
30/40
aR-160
37/50
aR-200
45/60
aR-250
Table 13.6 200-240 V, IP55/Nema 12 and IP66/Nema 4X
TM
AF-600 FP
Design and Installation Guide
Recommended max
AF-600 3-
fuse
gG-25
gG-32
gG-63
gG-125
gG-150
aR-160
aR-200
aR-250
Recommended max
fuse
gG-32
gG-80
gG-100
gG-160
aR-160
aR-200
1000/1350
aR-250
Table 13.7 380-480 V, IP20/Open Chassis
DET-768b
Recommended fuse
phase
size
[kW]/[HP]
0.75/1
1.5/2
gG-16
2.2/3
3.7/5
5.5/7.5
gG-20
7.5/10
11/15
15/20
gG-50
18.5/25
22/30
30/40
gG-80
37/50
45/60
gG-125
55/75
aR-160
75/100
aR-250
90/125
110/150
aR-300
132/200
aR-350
160/250
aR-400
200/300
aR-500
250/350
aR-630
315/450
aR-700
355/500
400/550
aR-900
450/600
500/650
aR-1600
560/750
630/900
aR-2000
710/1000
800/1200
aR-2500
Recommended max
fuse
gG-25
gG-32
gG-63
gG-125
gG-150
aR-160
aR-250
aR-300
aR-350
aR-400
aR-500
aR-630
aR-700
aR-900
aR-1600
aR-2000
aR-2500
13