GE AF-600 FP Series Design And Installation Manual page 48

Fan & pump drive
Hide thumbs Also See for AF-600 FP Series:
Table of Contents

Advertisement

Application Set-Up Examples
Table 6.6 Speed Reference (using a manual potentiometer)
Table 6.7 Speed Up/Down
TM
AF-600 FP
Design and Installation Guide
Parameters
Function
Setting
AN-10 Terminal
53 Low Voltage
0.07V*
AN-11 Terminal
10V*
53 High Voltage
AN-14 Terminal
0RPM
53 Low Ref./
Feedb. Value
AN-15 Terminal
1500RPM
53 High Ref./
Feedb. Value
* = Default Value
Notes/comments:
Parameters
Function
Setting
E-01 Terminal 18
[8] Start*
Digital Input
E-03 Terminal 27
[19] Freeze
Digital Input
Reference
E-04 Terminal 29
[21] Speed
Digital Input
Up
E-05 Terminal 32
[22] Speed
Digital Input
Down
* = Default Value
Notes/comments:
DET-768b
S p e e d
R e f e r e n c e
S t a r t ( 1 8 )
F r e e z e r e f ( 2 7 )
S p e e d u p ( 2 9 )
S p e e d d o w n ( 3 2 )
Illustration 6.3 Illustration for Table 6.7
Table 6.8 RS-485 Network Connection
Parameters
Function
Setting
O-30 Protocol
Modbus*
O-31 Address
1*
O-32 Drive Port
9600*
Baud Rate
* = Default Value
Notes/comments:
Select protocol, address and
baud rate in the above
mentioned parameters.
45
6
6

Advertisement

Table of Contents
loading

Table of Contents