Installation Consideration
When unscreened cables are used, some emission requirements are not complied with, although the immunity
requirements are observed.
In order to reduce the interference level from the entire system (unit + installation), make motor and brake cables as short
as possible. Avoid placing cables with a sensitive signal level alongside motor and brake cables. Radio interference higher
than 50 MHz (airborne) is especially generated by the control electronics.
7.1.2 Emission Requirements
According to the EMC product standard for adjustable speed frequency converters EN/IEC61800-3:2004 the EMC
requirements depend on the intended use of the frequency converter. Four categories are defined in the EMC product
standard. The definitions of the four categories together with the requirements for mains supply voltage conducted
emissions are given in Table 7.2:
Category
Definition
C1
Frequency converters installed in the first environment (home and office) with a
supply voltage less than 1000 V.
C2
Frequency converters installed in the first environment (home and office) with a
7
7
supply voltage less than 1000 V, which are neither plug-in nor movable and are
intended to be installed and commissioned by a professional.
C3
Frequency converters installed in the second environment (industrial) with a supply
voltage lower than 1000 V.
C4
Frequency converters installed in the second environment with a supply voltage
equal to or above 1000 V or rated current equal to or above 400 A or intended for
use in complex systems.
Table 7.2 Categories
When the generic emission standards are used the frequency converters are required to comply with the limits in Table 7.3:
Environment
First environment
(home and office)
Second environment
(industrial environment)
Table 7.3 Limits
58
TM
AF-600 FP
Generic standard
EN/IEC61000-6-3 Emission standard for residential, commercial and
light industrial environments.
EN/IEC61000-6-4 Emission standard for industrial environments.
Design and Installation Guide
DET-768b
Conducted emission requirement
according to the limits given in
EN55011
Class B
Class A Group 1
Class A Group 2
No limit line.
An EMC plan should be made.
Conducted emission requirement
according to the limits given in EN55011
Class B
Class A Group 1

Advertisement