General Specifications

5 General Specifications
Mains supply (L1, L2, L3):
Supply voltage
Supply voltage
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the drive continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque
cannot be expected at mains voltage lower than 10% below the drive's lowest rated supply voltage.
Supply frequency
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cos ϕ) near unity
Switching on input supply L1, L2, L3 (power-ups)
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100kAIC RMS symmetrical Amperes, 500/600/690 V
maximum.
Motor output (U, V, W):
Output voltage
Output frequency
Switching on output
Ramp times
* Voltage and power dependent
Torque characteristics:
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
Starting torque (Variable torque)
Overload torque (Variable torque)
Torque rise time in (independent of fsw)
Torque rise time in FLUX (for 5kHz fsw)
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
2)
Voltage level, logic '0' NPN
2)
Voltage level, logic '1' NPN
Maximum voltage on input
Pulse frequency range
(Duty cycle) Min. pulse width
Input resistance, R
i
AF-650 GP High Power Operating Instructions
380-480 V ±10%
525-690 V ±10%
3.0 % of rated supply voltage
≥ 0.9 nominal at rated load
maximum 1 time/ 2 min.
over-voltage category III/pollution degree 2
0 - 100% of supply voltage
0.01 - 3600 sec.
maximum 160% for 60 sec.
maximum 180% up to 0.5 sec.
maximum 160% for 60 sec.
maximum 110% for 60 sec.
maximum 110% for 60 sec.
18, 19, 27
50/60 Hz ±5%
5
5
(> 0.98)
0 - 800* Hz
Unlimited
1)
1)
1)
1)
10ms
1ms
4 (6)
1)
, 29, 32, 33,
PNP or NPN
0 - 24V DC
< 5V DC
> 10V DC
> 19V DC
< 14V DC
28V DC
0 - 110kHz
4.5ms
approx.4kΩ