Maximum Scale Value - Mitsubishi Electric ME96SSEA-MB User Manual

Electronic multi-measuring instrument
Hide thumbs Also See for ME96SSEA-MB:
Table of Contents

Advertisement

6. Other
6.2.

Maximum Scale Value

Settable primary voltage, primary current, and standard maximum scale value are shown in the tables below.
Maximum scale value of each item
Measurement element
Current,
Setting of current maximum
Current demand
scale =SP.
Voltage
In the
1-phase 2-wire, 3-phase 3-wire
case
with VT
3-phase 4-wire
(Note 2)
At direct
1-phase 2-wire,
input
3-phase 3-wire
1-phase 3-wire
(Phase voltage /
Line voltage)
3-phase 4-wire
(Phase voltage /
Line voltage)
Active power,
Note1: At direct voltage setting, VT ratio = 1. The specific power is according
to the table on the right.
Note2: For convenience of scale, this is rounded off to the nearest whole
number.
Maximum scale value
CT
Primary current
VT
Primary
voltage×150/110
VT
Primary voltage
(Phase
voltage)×150/110
VT
Primary voltage
(Line
voltage)×√3×150/110
110V
150V
220V
300V
440V
600V
110/220V
150V/300V
220/440V
300V/600V
63.5/110V
100/150V
100/173V,
150/300V
110/190V
220/380V,
230/400V,
300/600V
240/415V,
254/440V
277/480V
400/640V
(Note 1)
VT ratio×CT
ratio
×specific
power(100%)kW
Specific power value for scale calculation
Phase line
CT
type
Secondary
At direct input
(Line
5A
In the case with VT
(Line
1-phase
2-wire
At direct input
(Line
1A
In the case with VT
(Line
5A
1-phase
Without VT
3-wire
(Line
1A
At direct input
(Line
5A
In the case with VT
(Line
3-phase
3-wire
At direct input
(Line
1A
In the case with VT
(Line
At direct input
5A
In the case with VT
(Phase
3-phase
4-wire
At direct input
1A
In the case with VT
(Phase
49
Specific power
Rated voltage
value (100%)
110V
0.5kW
220V
1.0kW
voltage)
440V
2.0kW
100V, 110V
0.5kW
voltage)
220V
1.0kW
110V
0.1kW
220V
0.2kW
voltage)
440V
0.4kW
100V, 110V
0.1kW
voltage)
220V
0.2kW
220V
1.0kW
440V
2.0kW
voltage)
220V
0.2kW
440V
0.4kW
110V
1.0kW
220V
2.0kW
voltage)
440V
4.0kW
100V, 110V
1.0kW
voltage)
220V
2.0kW
110V
0.2kW
220V
0.4kW
voltage)
440V
0.8kW
100V, 110V
0.2kW
voltage)
220V
0.4kW
63.5/110V
1.0kW
100/173V
2.0kW
110/190V
220/380V,
230/400V,
4.0kW
240/415V,
254/440V
277/480V
5.0kW
63.5V
1.0kW
100V, 110V,
voltage)
2.0kW
115V, 120V
63.5/110V
0.2kW
100/173V
0.4kW
110/190V
220/380V,
230/400V,
0.8kW
240/415V,
254/440V
277/480V
1.0kW
63.5V
0.2kW
100V, 110V,
voltage)
0.4kW
115V, 120V

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Me96ssha-mbMe96ssra-mb

Table of Contents