6. Other

6.5. Measurement Characteristic

■Metering actions in other than operation mode
Status
Several seconds
No measurement
just after turning on
the auxiliary power
supply
(Backlight is lit, and
LCD is not lit.)
Setting mode,
Same actions as in
Set value
operation mode
confirmation mode
Password protection
mode
During power failure No measurement
■Metering actions in input status
Measurement
items
0A when the input current is less than 0.005A
Current (A)
Current
demand (DA)
0V when the input voltage (line voltage) is less than11V.
Voltage (V)
For 3-phase 4-wire, 0V when the line to neutral voltage
is less than 11V or the line to line voltage is less than
19V.
For 1-phase 3-wire, 0V when the voltage between
P1-P3 is less than 22V.
Active power (W)
0W for total when the current and the voltage are 0A
and 0V for all 3 phases.
0W for each phase when the current of phase n is 0A or
the voltage of phase n is 0V.
(where n = 1,2 or 3)
1.0 for total when the current and the voltage are 0A and 0V for all 3 phases.
Power factor (PF)
1.0 for each phase when the current of phase n is 0A or the voltage of phase n is 0V. (where n = 1,2 or 3)
When the input voltage of phase1 is low voltage, ---- will
Frequency (Hz)
be displayed. Input 22V or more.
For effective value measurement
Harmonic current
: When the current is 0A, 0A is displayed. (Each phase)
(HI)
: When the voltage of phase1 is 0V or the frequency is
less than 44.5Hz, ---- is displayed for all phases.
For effective value measurement
Harmonic Voltage
: When the current is 0V, 0V is displayed. (Each phase)
(HV)
: When the voltage of phase1 is 0V or the frequency is
less than 44.5Hz, ---- is displayed for all phases.
Operating Time
999999 hour is displayed if it is over 999999.
Note1: Input current and input voltage means the input to the instrument. They are not to primary sides of VT, CT.
Note2: For direct measurement, it does not input upper maximum scale value.
Measurement
Display
No display
No display of
measured value
No display
Actions
When it is over the upper limit of the possible display
range (9999), the upper limit of the possible display
range (9999) is displayed.
When it is over the upper limit of the possible display
range (9999), the upper limit of the possible display
range (9999) is displayed.
(Note 2)
When it is over the upper limit of the possible display
range (9999), the upper limit of the possible display
range (9999) is displayed.
When the frequency is less than 44.5Hz or over
99.9Hz, ---- is displayed.
For content factor measurement
: When the 1st current harmonic is 0A, 0% is
displayed. (Each phase)
: When the voltage of phase1 is 0V or the frequency is
less than 44.5Hz, ---- is displayed for all phases
For content factor measurement
: When the voltage is 0V, 0% is displayed. (Each
phase)
: When the voltage of phase1 is 0V or the frequency is
less than 44.5Hz, ---- is displayed for all phases
54