Appendix; Error Correction - Beckhoff KL3403 Series Documentation

3-phase power measurement terminals
Hide thumbs Also See for KL3403 Series:
Table of Contents

Advertisement

6

Appendix

6.1

Error correction

The following table shows typical errors and how to fix them.
Error
The KL3403 indicates
negative power
consumption, despite the
fact that a consumer is
connected.
An upstream residual
current circuit breaker
trips.
They want to measure
DC, but the KL3403 does
not show any meaningful
values.
Measuring inaccuracies
occur with large currents.
Measuring inaccuracies
occur when measuring
low DC voltages.
KL3403
Cause
• The connection of one or several
current circuits is reversed.
• Current and voltage circuits are not
connected correspondingly.
Example: Phase L1 is connected to
the voltage circuit for L1 (terminal
point 1 [} 29]), but the current
transformer connected to phase L1
is connected to I
(terminal point 6
L2
[} 29]).
A phase is connected to the neutral
conductor.
The DC filter of the KL3403 are
switched on (delivery state).
Overload at the current inputs of the
terminal (see chapter Measuring error
due to input overload [} 60]).
In the range 10 to 20 V, the voltage inputs of the KL3403 exhibit a small non-
linearity (see chapter Measuring error with DC voltage measurement [} 63]).
Version: 3.1.0
Remedy
Check the wiring!
Check the wiring!
Switch off the DC filters for the KL3403
(using the configuration software KS2000
[} 41] or the register communication
(register R32.4 [} 54])) for measuring
direct voltage and DC.
• Use a terminal type with higher rated
current (e.g. KL3403-0010 [} 19])
• Use current transformers with a higher
ratio.
Appendix
59