KS2000 Configuration Software
Watchdog timer active (R32 [} 54].2)
You can deactivate the watchdog timer here (the default is activated).
DC filter active (R32.4 [} 54])
Here you can disable the DC filter (default: enabled).
CosPhi, signed (R32.5 [} 54])
Here you can disable the signed representation for CosPhi (default: enabled).
Energy measurement inverted (R32.6 [} 54])
Here you can enable sign inversion for the energy measurement (default: disabled).
Flexible process image active (R32.3 [} 54])
Here you can enable/disable the flexible process image [} 50] (default:
• disabled for KL3403-0000, KL3403-0010, KL3403-0025, KL3403-0026, KL3403-0333,
• enabled for KL3403-0020, KL3403-0022)
Automatically clear minimum and maximum values (R32.7 [} 54])
Here you can enable automatic deletion of the minimum and maximum current, voltage and power values
(default: disabled).
Register values
Energy consumption scaling (R35 [} 54])
Here you can change the scaling of the energy consumption measurement. Default: 4
(KL3403-0000 /-002x /-0333: 0,01 kWh, KL3403-0010: 0,05 kWh).
Minimum input voltage - undervoltage threshold (R36 [} 54])
Here you can change the undervoltage threshold (resolution: 0.1 V).
If the mains voltage falls below the specified undervoltage threshold (default: 10 V), the red error LED is
triggered, and the error bit (SB1.6 [} 48]) is set in status byte 0.
Current transformer ratio (R37 [} 54])
The KL3403 can take the transformer ratio of a connected current transformer into account for the measured
value output.
Here you can select the transformer ratio of a connected current transformer and enable this scaling with the
option field User scaling (R32.0 [} 54]).
Note the permissible range of the measured value output
The KL3403 should only take the transformer ratio into account if the calculated resulting current
does not exceed the value 65535!
If the calculated result does exceed 65535, the transformer ratio should be taken into account in the
PLC.
Measuring cycle time (R39 [} 55])
Here you can change the measuring cycle time (resolution: 1 ms) (default: 200 ms).