TECHNICAL DATA
The unit is designed for application with the ambient temperature ranging from +1 °C to +40 °C and relative humidity up to 80 %.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above
the dew point temperature of the transported air.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
•
IP22 for the unit connected to the air ducts
•
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
Unit voltage [V /50 (60) Hz]
Maximum unit power [W]
Maximum unit current [A]
Maximum air flow [m
3
/h]
Sound pressure level at 3 m distance [dBA]
Transported air temperature [°C]
Insulation
Connected air duct diameter [mm]
Heat recovery efficiency** [%]
Humidity recovery efficiency** [%]
Heat exchanger type
Heat exchanger material
SEC class for the units with an A2 controller
SEC class for the units with an A14 controller
*The unit is equipped with an enthalpy heat exchanger and does not require condensate drainage
**Heat and humidity recovery efficiency according to EN 13141-7
VUT/VUE 300 V2 mini EC
C
ø122
495
447
78
105
154
MODEL
VUT/VUE 300 H2 mini EC A14
www.ventilation-system.com
MODEL
714
246
154
80
TECHNICAL DATA
VUT 300 V2/H2 mini EC
55 - 79
polystyrene
287
A
C
ø122
447
B
A
150
150
198
164
VUE 300 V2/H2 mini EC*
1~ 230
165
1.3
300
33
from -25 up to +60
20 mm mineral wool
G4
Ø125
32
cross-flow
polymerized cellulose
B
A
VUT/VUE 300 H2 mini EC
810
714
B
B
110
110
255
295
28
51 - 73
26 - 45
C
287
A
171
135
42
143
C
43
43
63
63
5