DESIGN AND FUNCTIONING

The unit has the following operating principle: warm stale extract air from the room flows into the unit, where it is filtered by the extract
filters, then air flows through the heat exchanger and is exhausted outside by the extract fan. Cold fresh air from the outside flows into
the unit, where it is cleaned by the supply filters. Then the air flows through the heat exchanger and is directed to the room with the
supply fan. Heat energy of warm extract air is transferred to clean intake fresh air from the outside and warms it up. The air flows are fully
separated while flowing through the heat exchanger. Heat recovery minimizes heat losses, which reduces the cost of space heating in
the cold season.
VUT/VUE 300 V2 mini EC
Extract air
Supply air
Freeze protection
The heat exchanger freeze protection function of the unit is implemented with a temperature sensor (for units with an A14 control panel)
or a thermostat (for units with an A2 control panel). The temperature sensor is installed in the exhaust air duct downstream of the heat
exchanger. In case of a freezing danger the supply fan is turned off and the heat exchanger is warmed up with warm extract air flow. The
recommended sensor or thermostat operating temperature is +3 °C (exhaust air temperature). If necessary, this setting can be changed
within the software. To set the thermostat temperature set point, set the temperature control knob into a respective position.
Extract filter
Humidity sensor
(option - only for A14 automation)
Control unit
Supply fan
Drain pan
Drain pipe
Control unit
Humidity sensor
(option - only for A14 automation)
Extract filter
Supply fan
Heat exchanger
Drain pan
Drain pipe
6
UNIT OPERATION LOGIC
Intake air
Exhaust air
Extract air
Supply air
VUT/VUE 300 V2 mini EC
VUT/VUE 300 H2 mini EC
VUT/VUE 300 H2 mini EC
UNIT DESIGN
Supply filter
Intake air filter with higher level of filtering
Extract air temperature sensor
(option - only for A14 automation)
Heat exchanger
Extract fan
Thermostat
Supply filter
Supply air filter with higher level of filtering
Extract fan
Extract air temperature sensor
(option - only for A14 automation)
Thermostat
VUT/VUE 300 V2/H2 mini EC
(only for A2 automation)
(only for A2 automation)