4 Commissioning the BTS (Transmission Available)
4-30

Figure 4-26 Basic Attributes of Site Board (1)

6.
Click Special Alarm Switch Valid Level Configuration in the Basic Attributes of
Site Board dialog box. Check whether the configuration of the Gate Magnetism(Low
Level) is consistent with the actual alarm switch valid level of the Gate Magnetism,
as shown in
Figure
is high level, then
In normal conditions, the check box Gate Magnetism(Low Level) is deselected,
which means the Door Open Alarm is reported at a high level.
If the check box Gate Magnetism(Low Level) is selected, deselect the check box.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4-27. If the alarm switch valid level of the field Gate Magnetism
BTS3900(A) GSM
Commissioning Guide
Issue 02 (2009-04-20)