Wall Opening - Lindab WK45 Installation Booklet

Rectangular series 500 pa / 300 pa fire damper
Hide thumbs Also See for WK45:

Advertisement

EI 120 S Installation within vertical rigid wall
Wall minimum density 500 kg/m³
EI 120 S Installation within vertical rigid wall
Wall minimum density 500 kg/m³
EI 180 S Installation within vertical rigid wall
Wall minimum density 500 kg/m³
B
Nominal base of the damper
H
Nominal height of the damper
EI 120 S / EI 180 S Installations within vertical rigid wall
1.
Sealing indicated in the table
D1 Hole base: see table above
D2 Hole height: see table above
E
Damper protrusion from the wall: see table above
S
Wall minimum thickness: see table above
Installations within vertical light wall (plasterboard)
Refer to the section Construction supports characteristics for further
information.
Comply with the minimum distances indicated on section Minimum
distances

Wall opening

A opening must be provided in the wall as indicated in the table and
in the drawing
EI 90 S Installation within vertical light wall (plasterboard)
Wall rock wool density up to 100 kg/
m³ (optional)
EI 120 S Installation within vertical light wall (plasterboard)
Wall rock wool density up to 100 kg/
m³ (optional)
B
Nominal base of the damper
H
Nominal height of the damper
Hole size "D1 x D2"
Fire resistance classification
EI 120 S
From (B+80) x (H+80)
(500 Pa)
to (B+580) x (H+580)
EI 120 S
From (B+80) x (H+80)
(500 Pa)
to (B+110) x (H+110)
EI 180 S
From (B+80) x (H+80)
(500 Pa)
to (B+110) x (H+110)
Hole size "D1 x D2"
Fire resistance classification
EI 90 S
Da (B+75) x (H+75)
(500 Pa)
a (B+95) x (H+95)
EI 120 S
Da (B+100) x (H+100)
(500 Pa)
to (B+580) x (H+580)
Damper protrusion from
the wall "E"
[mm]
[mm]
205
205
185
EI 120S Installation within vertical rigid wall
1.
Plasterboard infill panel, thickness 12,5 mm, for rock wool sealing
2.
Rock wool, 100 kg/m³
3.
Self-drilling screw Ø 3,5 X 45 mm
D1 Hole base: see table above
D2 Hole height: see table above
E
Damper protrusion from the wall: see table above
Damper positioning
Fix the four flaps code WKGY100 on the four corners of the fire damp-
er (in corrispondence to the longer screws).
Position the damper in the opening so that the side of the closing
mechanism extends as indicated in the table and in the drawing.
Filling
Fill the space between the wall and the damper as indicated in the
table and in the drawing.
Damper protrusion from
the wall "E"
[mm]
[mm]
205
205
Wall minimum thickness "S"
[mm]
Mortar or plaster putty
100
Rock wool 100 kg/m³
100
with infill plasterboard
(thickness 12.5 mm)
140
Mortar sealing
Wall minimum thickness "S"
[mm]
Rock wool 100 kg/m³
100
with infill plasterboard
(thickness 12.5 mm)
100
Mortar or plaster putty
Sealing
sealing
Sealing
13/17