Download Print this page

Lindab WK45 Installation Booklet page 11

Rectangular series 500 pa / 300 pa fire damper
Hide thumbs Also See for WK45:

Advertisement

Fire Batt (Weichschott) sealings
Installation
EI 90 S Installation within vertical rigid wall with Fire Batt
(Weichschott) sealing
Rock wool 140 kg/m³ and endothermic varnish sealing
EI 90 S Installation within vertical light wall (plasterboard) with
Fire Batt (Weichschott) sealing
Rock wool 140 kg/m³ and endothermic varnish sealing
EI 90 S Installation within vertical light wall (gypsum blocks wall)
with Fire Batt (Weichschott) sealing
Rock wool 140 kg/m³ and endothermic varnish sealing
EI 120 S Installation within floor with Fire Batt (Weichschott)
sealing
Rock wool 140 kg/m³ and endothermic varnish sealing
The minimum distance between two or more paired installations
is 200 mm.
It is forbidden to pair three or more fire dampers.
1.
One air duct
Construction supports characteristics
The European standard for fire dampers foresees a precise correlation
between the wall/floor characteristics and the fire resistance class
obtained, as well as the correlation between wall/floor used for the
test and wall/floor used for the actual installation.
The test results obtained on a type of wall/floor are valid also for
walls/floor of the same type but with greater thickness and/or densi-
ty than those used in the test.
For plasterboard walls, the test results are also valid for walls with a
greater number of plasterboard layers on each side.
As a result, the indicated thickness and density characteristics are to
be considered as minimum values.
The wall/floor in which the fire dampers are installed must be fire
class certified according to the standards foreseen for the structure.
Rigid walls
Can be made with aerated concrete blocks, poured concrete, con-
crete panels, perforated cell elements in concrete or brick in accord-
ance with the following characteristics:
• minimum thickness 100 mm;
• minimum density 500 kg/m³.
The use of a reinforcing beam above the opening is recommended
for walls made from concrete blocks, bricks or in concrete cell ele-
ments.
For walls built with perforated elements, it is also recommended that
the area of the opening be made from full elements (for example
aerated concrete blocks) to guarantee the correct adhesion of the
mortar.
Fire dampers installed within vertical wall
a [mm]
b [mm]
70
50
70
50
70
50
-
-
2.
Separate air ducts
1.
Reinforcing beam
Light plasterboard vertical walls
During testing, light plasterboard walls have been used with the fol-
lowing characteristics:
• U-shaped horizontal metal frame (50 mm) and C-shaped vertical
frame (49 mm) made from 0,6 mm thick sheet metal;
• Vertical profiles placed with a maximum spacing of 625 mm be-
tween each other;
• Filling made of rock wool with density up to 100 kg/m³ (optional);
• Each side is made from two plasterboard layers 12,5 mm thick, un-
alinged to avoid alignment between the joints of the layer above
and below.
Fire dampers installed within floor
c [mm]
d [mm]
-
-
-
-
-
-
200
75
Paired installation
Yes. One air duct
Yes. One air duct
Yes. One air duct
No
11/17

Advertisement

loading