Wall Opening - Lindab WH45P Installation Booklet

Circular series - 500 pa / 300 pa fire damper
Hide thumbs Also See for WH45P:
Table of Contents

Advertisement

1.
Rock wool density up to 100 kg/m³ (optional)
2.
Plasterboard arch infill, thickness 12,5 mm for rock wool sealing
3.
Plasterboard thickness 12,5 mm
4.
Sealing indicated in the table
5.
Self-drilling screw Ø 3,5 X 45 mm
6.
Metal frame
D
Hole size: see table above
E
Damper protrusion from the wall: see table above
Lp Overlap length between fire damper and duct: see section Dimension
Installations within vertical light wall (gypsum blocks wall)
Refer to the section Construction supports characteristics for further
information.
Comply with the minimum distances indicated on section Minimum
distances

Wall opening

A opening must be provided in the wall as indicated in the table and
in the drawing
EI 90 S Installation within vertical light wall (gypsum blocks wall)
Wall minimum thickness 70 mm
Wall minimum density 995 kg/m³
Plaster putty sealing
ve (i↔o)
EI 120 S Installation within vertical light wall (gypsum blocks wall)
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Plaster putty sealing
ve (i↔o)
1.
Plaster putty
D
Hole size: see table above
S
Wall minimum thickness: see table above
E
Damper protrusion from the wall: see table above
Lp Overlap length between fire damper and duct: see section Dimension
"D" hole size
Fire resistance classification
From Ø + 25
EI 90 S
(500 Pa)
(circular hole)
From Ø + 25
EI 120 S
(500 Pa)
(circular hole)
Damper positioning
Position the damper in the opening so that the side of the closing
mechanism extends as indicated in the table and in the drawing.
Filling
Fill the space between the wall and the damper as indicated in the
table and in the drawing.
Damper protrusion from
the wall "E"
[mm]
[mm]
to Ø+35
230 + Lp
to Ø+35
215 + Lp
Wall minimum thickness "S"
[mm]
70
Plaster putty sealing
100
Plaster putty sealing
Sealing