Lindab WK45 Installation Booklet page 15

Rectangular series 500 pa / 300 pa fire damper
Hide thumbs Also See for WK45:

Advertisement

Floor opening
A opening must be provided in the floor as indicated in the table
and in the drawing
Damper positioning
Position the damper in the opening so that the side of the closing
mechanism extends as indicated in the table and in the drawing.
EI 90 S Installation within floor
Floor minimum density 650 kg/m³
EI 120 S Installation within floor
Floor minimum density 650 kg/m³
EI 180 S Installation within floor
Floor minimum density 2200 kg/m³
B
Nominal base of the damper
H
Nominal height of the damper
Installations within vertical wall with Fire Batt (Weichschott) sealing
Refer to the section Construction supports characteristics for further
information.
Comply with the minimum distances indicated on section Minimum
distances
Wall opening
A opening must be provided in the wall as indicated in the table and
in the drawing
Damper positioning
Position the damper in the opening so that the side of the closing
mechanism extends as indicated in the table and in the drawing.
Filling
Fill the space between the damper and the wall using Fire Batt
(Weichschott) sealing made from two rock wool panels with mini-
mum thickness of 50 mm and minimum density of 140 kg/m³.
The panels must be covered on both faces of the wall with endo-
thermic varnish type PROMASTOP E PASTE or HILTI CFS-CT (mini-
mum thickness of 1 mm) and with an internal perimeter sealant type
PROMASTOP E PASTE or HILTI CFS-S ACR (minimum thickness of 1
mm).
Hole size "D1 x D2"
Fire resistance classification
EI 90 S
From (B+130) x (H+130)
(500 Pa)
to (B+170) x (H+170)
EI 120 S
From (B+130) x (H+130)
(500 Pa)
to (B+170) x (H+170)
EI 180 S
From (B+130) x (H+130)
(500 Pa)
to (B+170) x (H+170)
Filling
Fill the space between the floor and the damper as indicated in the
table and in the drawing.
Damper protrusion from
the wall "E"
[mm]
[mm]
193
193
185
D1 Hole base: see table above
D2 Hole height: see table above
E
Damper protrusion from the floor: see table above
S
Floor minimum thickness: see table above
1.
Mortar M-10, EN998-2
Floor minimum thickness "S"
[mm]
100
Mortar sealing
150
Mortar sealing
140
Mortar sealing
Sealing
15/17