| w e s i m p l i f y c o n s t r u c t i o n 1 - 4 - 7 Technical Manual English FIRE DAMPER CIRCULAR SERIES FBC1 - 4 - 7 - 300 Pa Cert. N° 1812-CPR-1630, 1812-CPR-1632, 1812-CPR-1634 1 - 4 - 7 Installation type with fire resistance class Technical Manual...
Page 4
Test EN 1366-2 Classification EN 13501-3 Thermal fuse reliability ISO 10294-4 Certifications and approvals FBC1: n° 1812-CPR-1630 CE Certificate of Constancy of Performance FBC4: n° 1812-CPR-1632 Efectis FBC7: n° 1812-CPR-1634 Components Casing made from galvanized carbon steel. Microswitch - on request Air duct connection gasket.
Page 5
Vertical installation Horizontal installation (i↔o) Origin of fire irrelevant Pascal of depression Integrity Thermal insulation Smoke seal Cert. N° FBC1 1812-CPR-1630,FBC4 1812-CPR-1632,FBC7 1812-CPR-1634 Fire Batt (Weichschott) sealings EI 120 S EI 90 S EI 60 S EI 30 S...
Page 6
Wet method sealing Dry method sealing Vertical installation Horizontal installation (i↔o) Origin of fire irrelevant Pascal of depression Integrity Thermal insulation Smoke seal Cert. N° FBC1 1812-CPR-1630,FBC4 1812-CPR-1632,FBC7 1812-CPR-1634 We reserve the right to make changes without prior notice 6/34 rev 20-02...
Page 7
ovER vIEw 1 - 4 - 7 1 - 4 - 7 Mechanism type Manual Blade closing mode Automatic closing with thermal fuse. The control mechanism has a thermosensitive element that automatically closes the blade when the temperature in the duct exceeds 70°C.
Page 8
ovER vIEw 1 - 4 - 7 1 - 4 - 7 Temperature calibration of thermosensitive element for automatic damper closing 70 °C±7 °C Closing by remote control not available Motorized version not available We reserve the right to make changes without prior notice 8/34 rev 20-02...
TECHnICAL DATA 1 - 4 - 7 1 - 4 - 7 TECHnICAL DATA The sizes shown are in mm. Dimension Ø S blade exposition Weights Ø Weight We reserve the right to make changes without prior notice 9/34 rev 20-02...
InSTALLATIon 1 - 4 - 7 1 - 4 - 7 InSTALLATIon Installation of flexible connectors in order The sizes shown are in mm. It is recommended to perform a functional test before In- to balance out the ventilation ducts stallation to exclude possible damage during transport.
Page 11
InSTALLATIon 1 - 4 - 7 1 - 4 - 7 Minimum distances In accordance with Articles 7 and 13 of En 1366-2 respect the minimum distances indicated below. Minimum distances Vertical lateral wall Floor We reserve the right to make changes without prior notice 11/34 rev 20-02...
Page 12
InSTALLATIon 1 - 4 - 7 1 - 4 - 7 Construction supports characteristics • vertical profiles placed with a maximum spacing of 1000 The European standard for fire dampers foresees a precise correlation between the wall/floor characteristics and the mm between each other;...
Page 13
Apply the mineral fiber gaskets supplied with the damper at a distance of 15 mm from the seal. Fire damper model FBC1 Plasterboard arch infill, thickness 12,5 mm Self-drilling screw Ø 3,5 X 45 mm Rock wool, 100 kg/m³ or mortar or plaster putty...
Page 14
InSTALLATIon 1 - 4 - 7 1 - 4 - 7 Fire damper model FBC1, FBC4, FBC7 Ventilation duct Fire damper Mortar or plaster putty Vertical rigid wall, minimum density 550 kg/m³ Mineral fiber gasket (supplied with the damper) from nominal diameter min + 50 to nominal diameter max + 70...
Page 15
Apply the mineral fiber gaskets supplied with the damper at a distance of 15 mm from the seal. Fire damper model FBC1 (square hole) Wall rock wool density according to fire resistance class of the wall Metal frame Plasterboard arch infill, thickness 12,5 mm...
Page 16
InSTALLATIon 1 - 4 - 7 1 - 4 - 7 Fire damper model FBC1 (circular hole) Wall rock wool density according to fire resistance class of the wall Mineral fiber gasket (supplied with the damper) Metal frame Fire damper...
Page 17
InSTALLATIon 1 - 4 - 7 1 - 4 - 7 Fire damper model FBC4 (circular and square hole) Wall rock wool density according to fire resistance class of the Metal frame wall Ventilation duct PROMASTOP E PASTE or HILTI CFS-S ACR type sealant Fire damper Plasterboard, thickness 12,5 mm F type (EN 520) Plasterboard arch infill, thickness 12,5 mm...
Page 18
InSTALLATIon 1 - 4 - 7 1 - 4 - 7 Fire damper model FBC4, FBC7 (square hole) Wall rock wool density according to fire resistance class of the wall Self-drilling screw Ø 3,5 X 45 mm Metal frame Fire damper Plasterboard, thickness 12,5 mm F type (EN 520) Ventilation duct Rock wool, 100 kg/m³...
Page 19
InSTALLATIon 1 - 4 - 7 1 - 4 - 7 Fire damper model FBC4, FBC7 (circular hole) Wall rock wool density according to fire resistance class of the wall Self-drilling screw Ø 3,5 X 45 mm Metal frame Fire damper Plasterboard, thickness 12,5 mm F type (EN 520) Ventilation duct Rock wool, 100 kg/m³...
Page 20
Fire damper model FBC1, FBC4, FBC7 Mineral fiber gasket (supplied with the damper) From nominal diameter min + 0 to nominal diameter max + 70 Fire damper = min 100 mm for FBC1, FBC4 Mortar = min 150 mm for FBC7 Ventilation duct = 45 mm for FBC1, FBC4 Floor, minimum density 550 kg/m³...
Page 21
Wall minimum density ≥550 kg / m³ or light wall (plasterboard): PROMASTOP E PASTE or HILTI CFS-S ACR type sealant type A (FBC1) / tiype F (FBC4, FBC7) (EN 520) PROMASTOP E PASTE or HILTI CFS-CT endothermic varnish Mineral fiber gasket (supplied with the damper)
Page 22
PROMASTOP E PASTE or HILTI CFS-S ACR type sealant Nominal diameter + 600 max PROMASTOP E PASTE or HILTI CFS-CT endothermic varnish = min 100 mm for FBC1, FBC4 Ventilation duct = min 150 mm for FBC7 Mineral fiber gasket (supplied with the damper) = 45 mm for FBC1, FBC4 Rock wool panel 50 mm thick with 140 kg/m³...
ELEC TRICAL ConnEC TIonS 1 - 4 - 7 1 - 4 - 7 ELEC TRICAL ConnEC TIonS Electrical wiring Electrical connections must be done by qualified and trained people. Switch off the power supply before starting any work on the electric elements. never switch on the power supply during electrical connections.
MAInTEnAnCE AnD InSPEC TIonS 1 - 4 - 7 1 - 4 - 7 MAInTEnAnCE AnD InSPEC TIonS Fire dampers and control mechanisms do not require rou- tine maintenance. Extraordinary maintenance (repairs) and periodic inspec- tion operations are the responsibility of the ventilation sys- tem operator.
Page 25
SELEC TIon 1 - 4 - 7 1 - 4 - 7 SELEC TIon Air flow rates in relation to the diameter Ø Front section Net section Maximum air flow Maximum speed m² m² m³/h 0,008 0,002 0,012 0,004 0,020 0,010 0,031...
Page 27
SELEC TIon 1 - 4 - 7 1 - 4 - 7 Sound spectrum table Correction used to estimate the octave band spectrum (values to be added to the noise levels in dB(A)) Ø100 Speed (m/s) -0,8 -4,8 -8,1 -10,7 -9,7 -13,7...
ACCESSoRIES AnD SPARE PAR TS 1 - 4 - 7 1 - 4 - 7 ACCESSoRIES AnD SPARE PAR TS Arch infill panels for plasterboard installation from Ø 100 to Ø 200 (thickness 12.5 mm) TAMP-WH25-Ø Closed damper microswitch FBCFC Thermofuse with 70 °C setting for FBC FBC70 We reserve the right to make changes without prior notice...
Fire damper EI 120 S without valve and without microswitch Ø 200 FBC7-S0-200 Fire damper EI 60 S without valve and without microswitch Ø 100 FBC1-S0-100 Fire damper EI 90 S without valve and with microswitch Ø 125 FBC4-S1-125 We reserve the right to make changes without prior notice...
(plasterboard) with minimum thickness 100 • Installation with Fire Batt (weichschott) sealing within concrete floors or aerated concrete with minimum thick- ness 100 mm (FBC1, FBC4,) o 150 mm (FBC7) and mini- mum density 550 kg/m³ • Fire resistance characteristics independent from direc- tion of the source of the fire according to En 1366-2 ar- ticle 6.2...
REvISIon InDEx 1 - 4 - 7 1 - 4 - 7 REvISIon InDEx Revision n° Date of issue Description 19/11 2019/11 First issue 20/02 2020/02 Ø180 remove We reserve the right to make changes without prior notice 31/34 rev 20-02...
Page 33
- Fire dampers are manufactured by MP3 Srl www�mp3-italia�it As the manufacturer is constantly improving its products, the aesthetic or dimensional features, the technical data, the equipment and accessories indicated could be subject to variations.
Page 34
At Lindab, good thinking is a philosophy that guides us in everything we do. We have made it our mission to create a healthy indoor climate – and to simplify the construction of sustainable buildings. We do that by designing innovative products and solutions that are easy to use, as well as offering efficient availability and logistics.