Lindab WH45P Installation Booklet

Circular series - 500 pa / 300 pa fire damper
Hide thumbs Also See for WH45P:

Advertisement

Quick Links

WH45P
LINDAB SAFE
Installation booklet
English
CIRCULAR SERIES WH45P - 500 Pa / 300 Pa
Cert. N° 1812-CPR-1107 EN 15650
*1MUBWH45PUEN* rev 19-05
*1MUBWH45PUEN-LIND* rev 19-05
*1MUBWH45PUEN*
*1MUBWH45PUEN-LIND*
www.mp3-italia.it
www.lindab.com - Fire dampers are manufactured by MP3 Srl www.mp3-italia.it
For further information please refer to the Technical Manual.
As the manufacturer is constantly improving its products, the aesthetic or dimensional features, the technical data, the equipment and acces-
sories indicated could be subject to variations.
This is a 16 page installation booklet.

Advertisement

Table of Contents
loading

Summary of Contents for Lindab WH45P

  • Page 1 WH45P LINDAB SAFE Installation booklet English CIRCULAR SERIES WH45P - 500 Pa / 300 Pa Cert. N° 1812-CPR-1107 EN 15650 *1MUBWH45PUEN* rev 19-05 *1MUBWH45PUEN-LIND* rev 19-05 *1MUBWH45PUEN* *1MUBWH45PUEN-LIND* www.mp3-italia.it www.lindab.com - Fire dampers are manufactured by MP3 Srl www.mp3-italia.it For further information please refer to the Technical Manual.
  • Page 2 OVER VIEW Fire resistance classification according to EN 13501-3-2009 „ EI 180 S EI 120 S EI 90 S EI 60 S EI 30 S (500 Pa) (500 Pa) (500 Pa) (500 Pa) (500 Pa) EI 90 S Installation within vertical rigid wall Wall minimum thickness 100 mm Ø...
  • Page 3 Fire Batt (Weichschott) sealings † EI 120 S EI 90 S EI 60 S EI 30 S (300 Pa) (300 Pa) (300 Pa) (300 Pa) EI 120 S Installation within vertical rigid wall with Fire Batt (Weichschott) sealing Wall minimum thickness 100 mm Ø...
  • Page 4: Electrical Connections

    Temperature calibration of thermosensitive element for auto- Siemens motorized version † matic damper closing Manual closing switch 70 °C±7 °C (Standard) Manual opening lever 95 °C±9 °C (On request). Screwdriver Position indicator Belimo motorized version † Manual closing switch Manual opening lever Position indicator Blade locking lever Blade closing mode...
  • Page 5 SA (open damper) microswitch - on request Magnet - on request Magnet cables for wiring 24 V DC power supply Magnet WH45P - Motorized version † SC/SA microswitches position † Belimo servomotor: "NC" contact of SC microswitch. When the fire blade is closed the circuit BFL24T, BFN24T, BF24T, BFL230T, BFN230T, BF230T.
  • Page 6: Electrical Specifications

    Negative (DC) or neutral (AC) Positive (DC) or phase (AC) Phase Neutral S1 Common closed damper microswitch S2 Normally closed, closed damper microswitch S3 Normally opened, closed damper microswitch S4 Common open damper microswitch S5 Normally closed, open damper microswitch S6 Normally opened, open damper microswitch Motorized fire dampers electical wiring To connect the dampers to the power supply, proceed as follows:...
  • Page 7: Technical Data

    TECHNICAL DATA Dimension „ Ø S1 blade exposition S2 blade exposition Ø S1 blade exposition S2 blade exposition Overlap length between fire damper and duct MAINTENANCE AND INSPEC TIONS Fire dampers and control mechanisms do not require routine main- Damper cleaning is included in the ordinary maintenance activities tenance.
  • Page 8: Installation

    INSTALLATION The sizes shown are in mm. • Attention: fire resistance classification for transfer application is It is recommended to perform a functional test before Installation to conform to section Fire resistance classification according to EN exclude possible damage during transport and another test immedi- 13501-3-2009 limited to EI 90S if the ducted classification is higher.
  • Page 9 Length of end cap with mesh depending on fire damper di- Minimum distances „ ameter Ø. It is recommended to keep enough space for using the control mechanism or for maintenance. Ø In accordance with Articles 7 and 13 of EN 1366-2 respect the mini- mum distances indicated below.
  • Page 10 Fire dampers installed within vertical wall Fire dampers installed within floor Installation a [mm] b [mm] c [mm] d [mm] EI 180 S Installation within vertical rigid wall Mortar sealing EI 120 S Installation within vertical rigid wall Mortar or plaster putty sealing EI 90 S Installation within vertical rigid wall Plasterboard and rock wool 100 kg/m³...
  • Page 11 Light plasterboard vertical walls Gypsum blocks light walls † † During testing, light plasterboard walls have been used with the fol- Gypsum blocks wall can be built with special solid gypsum blocks lowing characteristics: with interlocking shaped edges as indicated in the supplier's instruc- •...
  • Page 12 Wall opening Filling † † A opening must be provided in the wall as indicated in the table and Fill the space between the wall and the damper as indicated in the in the drawing table and in the drawing. Damper positioning †...
  • Page 13: Wall Opening

    Rock wool density up to 100 kg/m³ (optional) Plasterboard arch infill, thickness 12,5 mm for rock wool sealing Plasterboard thickness 12,5 mm Sealing indicated in the table Self-drilling screw Ø 3,5 X 45 mm Metal frame Hole size: see table above Damper protrusion from the wall: see table above Lp Overlap length between fire damper and duct: see section Dimension Installations within vertical light wall (gypsum blocks wall)
  • Page 14 Installations within floor „ Refer to the section Construction supports characteristics for further Damper positioning † information. Position the damper in the opening so that the side of the closing Comply with the minimum distances indicated on section Minimum mechanism extends as indicated in the table and in the drawing. distances Filling †...
  • Page 15 Damper protrusion from “D” hole size Wall minimum thickness “S” Fire resistance classification the wall “E” Sealing [mm] [mm] [mm] EI 120 S Installation within rigid vertical wall with Fire Batt (Weichschott) sealing (Ø + 800 max) x (Ø + Rock wool 140 kg/ Wall minimum density 500 EI 120 S...
  • Page 16 Rock wool panel 50 mm thick with 140 kg/m³ density. PROMASTOP E PASTE or HILTI CFS-S ACR type sealant PROMASTOP E PASTE or HILTI CFS-CT endothermic varnish Hole size: see table above Damper protrusion from the wall: see table above Lp Overlap length between fire damper and duct: see section Dimension 16/16...