Rectangular series 500 pa / 300 pa fire damper
Hide thumbs Also See for WK45:

Advertisement

EI 120 S Installation within rigid vertical wall with Fire Batt (Weichschott) sealing
Wall minimum density 500
kg/m³
EI 120 S Installation within vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing
Wall rock wool density up to 100
kg/m³ (optional)
EI 120 S Installation within vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing
Wall minimum density 995
kg/m³
B
Nominal base of the damper
H
Nominal height of the damper
Installation within floor with Fire Batt (Weichschott) sealing
Refer to the section for further information.
Comply with the minimum distances indicated on section Minimum
distances
Floor opening
A opening must be provided in the floor as indicated in the table
and in the drawing
Damper positioning
Position the damper in the opening so that the side of the closing
mechanism extends as indicated in the table and in the drawing.
EI 120 S Installation within floor and Fire Batt (Weichschott) sealing
Floor minimum density 650 kg/m³
B
Nominal base of the damper
H
Nominal height of the damper
16/17
Hole size "D1 x D2"
Fire resistance classification
EI 90 S
(B+800 max) x (H+800
(300 Pa)
EI 90 S
(B+800 max) x (H+800
(300 Pa)
EI 90 S
(B+800 max) x (H+800
(300 Pa)
Hole size "D1 x D2"
Fire resistance classification
EI 120 S
(B+800 max) x (H+800
(300 Pa)
Damper protrusion from
the wall "E"
[mm]
[mm]
205
max)
205
max)
205
max)
D1 Hole base indicated in the table
D2 Hole height indicated in the table
E
Damper protrusion from the wall indicated in the table
1.
Rock wool panel 50 mm thick with 140 kg/m³ density.
2.
PROMASTOP E PASTE or HILTI CFS-S ACR type sealant
3.
PROMASTOP E PASTE or HILTI CFS-CT endothermic varnish
Filling
Fill the space between the damper and the floor using Fire Batt
(Weichschott) sealing made from two rock wool panels with mini-
mum thickness of 50 mm and minimum density of 140 kg/m³.
The panels must be covered on both faces of the wall with endo-
thermic varnish type PROMASTOP E PASTE or HILTI CFS-CT (mini-
mum thickness of 1 mm) and with an internal perimeter sealant type
PROMASTOP E PASTE or HILTI CFS-S ACR (minimum thickness of 1
mm).
Damper protrusion from
the wall "E"
[mm]
[mm]
205
max)
Wall minimum thickness "S"
[mm]
Rock wool 140 kg/
100
m³ and endothermic
varnish sealing
Rock wool 140 kg/
100
m³ and endothermic
varnish sealing
Rock wool 140 kg/
100
m³ and endothermic
varnish sealing
Floor minimum thickness "S"
[mm]
Rock wool 140 kg/
150
m³ and endothermic
varnish sealing
Sealing
Sealing