Lindab WK45 Installation Booklet page 9

Rectangular series 500 pa / 300 pa fire damper
Hide thumbs Also See for WK45:

Advertisement

Flexible connector must be normal flammability and in case of fire
the grounding bonding should disconnet to guarantee the com-
plete separation between fire damper and connected air duct.
When flexible connectors made of conductive material (e.g. alumi-
num) are used, no additional grounding bonding is required.
Despite flexible connector installation, the fire damper must be in-
stalled in the construction support so that its weight does not affect
damper's installation position both during normal operation and in
case of fire.
It is recommended not to compress flexible connectors in the in-
stallation phase.
Flexible connector must be at least 100mm long and in order that
possible duct thermal expansions are balanced.
Take care that the flexible connector does not interfer with opening
/ closing movement of the blade.
Transfer Application (application not connected to air ducts on
one or both sides)
Following tests performed as per EN 1366-2, section 6.3.6 Standard,
it is possible to install the fire damper free from air duct from one or
both sides.
• Attention: fire resistance classification for transfer application is
conform to section Fire resistance classification according to EN
13501-3-2009 limited to EI 120S if the ducted classification is high-
er.
• End cap with mesh shall be mounted on the side not connected
to air duct.
• End cap with mesh is made from galvanized steel sheet and in-
cludes nuts and screws for fixing on fire damper.
• End cap with mesh is supplied loose from the fire damper.
Components (Transfer Application)
1.
End cap with mesh
2.
Fire damper
Technical data (Transfer Application)
1.
Mechanism side
2.
Mechanism opposite side
3.
End cap with mesh
L1 End cap length mechanism side
3.
M10 nut
4.
M10 screw
L2 End cap length mechanism
opposite side
H
Nominal height of fire damper
Length of end cap with mesh depending on fire damper
height H.
H
200
250
300
350
400
450
500
550
600
650
700
750
800
H
Nominal height of fire damper
L1
End cap length mechanism side
L2
End cap length mechanism opposite side
Minimum distances
It is recommended to keep enough space for using the control
mechanism or for maintenance.
In accordance with Articles 7 and 13 of EN 1366-2 respect the mini-
mum distances indicated below.
L1
L2
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
100
100
100
100
150
150
150
150
9/17