22 Maintenance and service

In this chapter

22.1 Maintenance safety precautions

22.1.1 To prevent electrical hazards

RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452191-1B – 2020.10
NOTICE
Maintenance MUST be done by an authorized installer or service agent.
We recommend performing maintenance at least once a year. However, applicable
legislation might require shorter maintenance intervals.
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
Formula to calculate the quantity in CO
refrigerant × total refrigerant charge [in kg] / 1000
22.1
Maintenance safety precautions............................................................................................................................................ 133
22.1.1
To prevent electrical hazards................................................................................................................................. 133
22.2
Maintenance of the plate heat exchanger............................................................................................................................. 134
22.2.1
To clean the plate heat exchanger ........................................................................................................................ 134
22.3
About service mode operation............................................................................................................................................... 135
22.3.1
To use vacuum mode ............................................................................................................................................. 135
22.3.2
To recover refrigerant............................................................................................................................................ 135
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
NOTICE: Risk of electrostatic discharge
Before performing any maintenance or service work, touch a metal part of the unit in
order to eliminate static electricity and to protect the PCB.
When performing service to inverter equipment:
1 Do NOT open the electrical component box cover for 10 minutes after turning
off the power supply.
2 Measure the voltage between terminals on the terminal block for power
supply with a tester and confirm that the power supply is shut off. In addition,
measure points as shown in the figure, with a tester and confirm that the
voltage of the capacitor in the main circuit is less than 50 V DC.
22
Maintenance and service
|
equivalent.
2
equivalent tonnes: GWP value of the
2
Installer and user reference guide
133