Daikin VRV IV W+ Series Installer And User Reference Manual page 110

Water-cooled system air conditioner
Hide thumbs Also See for VRV IV W+ Series:
Table of Contents

Advertisement

19
|
Electrical installation
Installer and user reference guide
110
In case of heat pump system
b
c
A1P
F1 F2 F1 F2 Q1 Q2
Q1 Q2
e
f
e
F1 F2
h
i
F1 F2
a Outdoor unit PCB (A1P)
b Unit A (master outdoor unit)
c Unit B (slave outdoor unit)
d Unit C (slave outdoor unit)
e Outdoor unit/other system transmission (F1/F2)
f Outdoor-outdoor unit transmission (Q1/Q2)
g Indoor unit
h Use the conductor of sheathed wire (2 wire) (no polarity)
i Terminal board (field supply)
In case of heat recovery system
TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT
F1
F2
F1
F2 Q1Q2
a
A1P
F
F
F
F
Q
Q
1
2
1
2
1
2
a Unit A (master outdoor unit)
b Unit B (slave outdoor unit)
c Unit C (slave outdoor unit)
d Outdoor unit PCB (A1P)
e Master/slave transmission (Q1/Q2)
f Outdoor/indoor transmission (F1/F2)
g Outdoor unit/other system transmission (F1/F2)
h BS unit
i Indoor unit
j Cooling-only VRV indoor unit / Heating-only Hydrobox unit
The interconnecting wiring between the outdoor units in the same piping system
must be connected to the Q1/Q2 (Out Multi) terminals. Connecting the wires to
the F1/F2 terminals results in system malfunction.
The wiring for the other systems must be connected to the F1/F2 (Out-Out)
terminals of the PCB in the outdoor unit to which the interconnecting wiring for
the indoor units is connected.
The base unit is the outdoor unit to which the interconnecting wiring for the
indoor units is connected.
d
Q1 Q2
F1
F2
F1
TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT
f
g
a
F1 F2
F1 F2
F1 F2
F1 F2
d
F1 F2 F1 F2
TO IN/D
TO OUT/D
UNIT
UNIT
h
b
c
A1P
A1P
Q
Q
Q
Q
1
2
1
2
F1 F2
i
e
e
g
F2 Q1 Q2
f
F1 F2 F1 F2
TO IN/D
TO OUT/D
UNIT
UNIT
h
F1 F2
F1 F2
F1 F2
i
j
F1 F2
F1 F2
VRV IV water-cooled system air conditioner
4P452191-1B – 2020.10
RWEYQ8~14T9Y1B