Maintenance And Service; Overview: Maintenance And Service; Maintenance Safety Precautions; To Prevent Electrical Hazards - Daikin RZAG71N V1B Series Installer's Reference Manual

Hide thumbs Also See for RZAG71N V1B Series:
Table of Contents

Advertisement

10 Maintenance and service

10.1 Overview: Maintenance and service

10.2 Maintenance safety precautions

10.2.1 To prevent electrical hazards

RZAG71~140N
Sky Air Alpha-series
4P695307-1A – 2024.02
NOTICE
Maintenance MUST be done by an authorised installer or service agent.
We recommend performing maintenance at least once a year. However, applicable
legislation might require shorter maintenance intervals.
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
Formula to calculate the quantity in CO
refrigerant × total refrigerant charge [in kg] / 1000
This chapter contains information about:
Maintenance safety precautions
The yearly maintenance of the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
NOTICE: Risk of electrostatic discharge
Before performing any maintenance or service work, touch a metal part of the unit in
order to eliminate static electricity and to protect the PCB.
When performing service to inverter equipment:
1 Do NOT open the electrical component box cover for 10 minutes after turning
off the power supply.
2 Measure the voltage between terminals on the terminal block for power
supply with a tester and confirm that the power supply is shut off. In addition,
measure points as shown in the figure, with a tester and confirm that the
voltage of the capacitor in the main circuit is less than 50 V DC. If the voltage
measured is still higher than 50  V  DC, discharge the capacitors in a safe
manner by using a dedicated capacitor discharge pen to avoid possibility of
sparking.
10
Maintenance and service
|
equivalent.
2
equivalent tonnes: GWP value of the
2
Installer reference guide
71