To Finish The Transmission Wiring; To Route And Fix The Power Supply - Daikin VRV IV W+ Series Installer And User Reference Manual

Water-cooled system air conditioner
Hide thumbs Also See for VRV IV W+ Series:
Table of Contents

Advertisement

19.4 To finish the transmission wiring

19.5 To route and fix the power supply

RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452191-1B – 2020.10
After installing the transmission wires inside the unit, wrap them along with the on-
site refrigerant pipes using finishing tape, as shown in figure below.
c
b
f
a
f
a Liquid pipe
b Gas pipe
c Finishing tape
d High pressure/low pressure gas pipe
e Transmission wiring (F1/F2)
f Insulator
NOTICE
When routing earth wires, secure clearance of 25  mm or more away from
compressor lead wires. Failure to observe this instruction properly may adversely
affect correct operation of other units connected to the same earth.
The power supply wiring can be routed from the front side. Exit the wiring via the
upper mounting hole.
f
d
e
A1P
19
Electrical installation
|
Installer and user reference guide
111