To Use Mode 2 - Daikin VRV IV W+ Series Installer And User Reference Manual

Water-cooled system air conditioner
Hide thumbs Also See for VRV IV W+ Series:
Table of Contents

Advertisement

20
|
Configuration

20.2.6 To use mode 2

Installer and user reference guide
120
Example:
Checking the content of parameter [1‑10] (to know how many indoor units are
connected to the system).
[A‑B]=C in this case defined as: A=1; B=10; C=the value we want to know/monitor:
1 Make sure the 7‑segment display indication is in the default situation (normal
operation).
2 Push BS1 one time.
Result: Mode 1 is accessed:
3 Push BS2 10 times.
Result: Mode 1 setting 10 is addressed:
4 Push BS3 one time; the value which is returned (depending on the actual field
situation), is the amount of indoor units which are connected to the system.
Result: Mode  1 setting 10 is addressed and selected, return value is
monitored information
5 To quit mode 1, push BS1 one time.
The master unit should be used to input field settings in mode 2.
Mode 2 is used to set field settings of the outdoor unit and system.
What
Changing and accessing the
setting in mode 2
To quit and return to the initial
status
Changing the value of the
selected setting in mode 2
Example:
Checking the content of parameter [2‑12].
[A‑B]=C in this case defined as: A=2; B=12; C=the value we want to know/change
1 Make sure the 7‑segment display indication is as during normal operation
(default situation when shipped from factory).
How
Once mode 2 is selected (push BS1 for more
than 5 seconds), you can select the wanted
setting. It is done by pushing BS2.
Accessing the selected setting's value is done by
pushing BS3 1 time.
Press BS1.
Once mode  2 is selected (push BS1 for more
than 5 seconds) you can select the wanted
setting. It is done by pushing BS2.
Accessing the selected setting's value is done
by pushing BS3 1 time.
Now BS2 is used to select the required value
of the selected setting.
When the required value is selected, you can
define the change of value by pushing BS3 1
time.
Press BS3 again to start operation according to
the chosen value.
VRV IV water-cooled system air conditioner
RWEYQ8~14T9Y1B
4P452191-1B – 2020.10

Hide quick links:

Advertisement

Table of Contents
loading