18.1.2 Refrigerant piping insulation
18.1.3 To select the piping size
RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452191-1B – 2020.10
▪
Use polyethylene foam as insulation material:
-
with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045 kcal/mh°C)
-
with a heat resistance of at least 120°C
▪
Insulation thickness
Ambient temperature
≤30°C
>30°C
INFORMATION
Please select the proper pipe sizes depending on the mode of your system. There are
2 possible modes:
▪
heat pump,
▪
heat recovery.
Determine the proper size using the following tables and reference figure (only for
indication).
In case of heat pump system
a
D
F
b
3
E
1
2
4
1,2 VRV DX indoor unit
3 Branch selector box (BP*)
4,5 RA DX indoor unit
a,b Indoor branch kit
x,y Outdoor multi connection kit
In case of heat recovery system
a
D
E
3
4
b
E
1
2
Humidity
75% to 80% RH
≥80% RH
B
B
A
x
C
y
G
5
B
B
A
x
C
y
18
Piping installation
|
Minimum thickness
15 mm
20 mm
B
B