EMC Statement These products are tested and thereby comply with the conditions of CE regulation, which established to offer sufficient protection against dangerous interference for installation. Installation and use of the equipment should comply with the instructions provided to avoid such interference due to the amount of radio frequency energy that generates by the equipment;...
IMPORTANT SAFETY INSTRUCTION WARNING: SAVE THESE INSTRUCTIONS!! WARNING: Manual contains important instructions of UPS and batteries during installation and maintenance. Follow this instruction at all time WARNING: It is recommended to install UPS in an ANSI/NFPA75 room in which temperature ...
Introduction The information provided in this manual covers On-Line 1000-3000VA uninterruptible power system (UPS). This manual contains basic functions, operating procedures, and emergencies, also including information on how to ship, store, handle, and install the equipment. Only detailed requirements of the UPS units described herein.
EPO port A customer-supplied switch can remotely use to open the EPO connection and shut off UPS output. Since EPO shuts down the UPS immediately without regular procedure and monitoring, UPS will require a manual restart to restore operation. 3.3 Connection to External Battery Pack External battery connections shall install by service personnel only.
Operation Necessary information for the operation of the unit is covered in this chapter. Normally UPS runs automatically, but on a few occasions such as just after installation, all procedures are described herein. 4.1 General Description As double conversion On-line UPS, it can convert clean single-phase power to support your critical system.
will also fix output frequency to 50Hz(220V) or 60Hz(110V) with ±0.25Hz. Users can set the UPS to bypass/shutdown whenever UPS malfunction occurred. Generator Mode can activate from the LCD panel too. 4.2 System Configuration The UPS device and battery make up the system. Depending on site and load requirements, certain additional options are available as tailored solutions.
Page 13
Button Display Status / Enter Button ON/OFF Button To turn UPS on and off, To check UPS status and confirm refer to Button Operation settings, refer to Button Operation Function Button To check UPS status and confirm settings, refer to Button Operation Button operation Cold Start function When the main power is disconnected from UPS, it is capable of starting with...
Turn on the UPS Ensure installation is correct and successful, and connect teh input power cable to a well-grounded outlet. Push the “on/off” bottom on the front panel for 3 seconds. UPS should start its inspection of internal function, main synchronization, and ...
Connect with factory-provided/approved communication cable Ensure your computer can install and support power management software. Note: Either USB Port or RS232 port, only one port will function at a time. 5.2 Connect UPS with interface Slot(Optional) SNMP Card allows UPS management and monitoring over a network or internet ...
To maintain the vitality of the batteries, please recharges the UPS at least 8 hours every six months. 6.3 Operation CAUTION: Ensure that all environmental concerns and requirements are met according to safety instruction; otherwise, the safety of installation personnel cannot be guaranteed since the unit may malfunction.
1. (For Tower model below 2KVA): Locate the front panel’s 2 tenons as the arrow indicated; Press the tenon and pull out lightly. Then push the front panel downward and pull out to remove the panel. (For Tower model 2000VA) Hold the top two corners of the front panel as arrow indicated;...
Restore 1. Check the UPS display; it should show “Manual Bypass Mode” with indications 2. Press the” Function” button for 3 seconds and toggle to “Manual Bypass.” 3. Press “Enter” to select. You will see the setting as “ON” displayed in LCD. 4.
Notice: For the 120V model (1.5K, 2K, 3K), the input 100 volt ratings must be derated by 10% to meet UL current requirements. Tower Model 1000 1500 2000 3000 Configuration Capacity (VA) 1000 VA 1500 VA 2000 VA 3000 VA Capacity (Watts) 900 W 1350 W 1800 W 2700 W...
Page 21
Configuration Capacity (VA) 1000 VA 1500 VA 2000 VA 3000 VA 2000 VA 3000 VA Capacity (Watts) 900 W 1350 W 1800 W 2700 W 1800W 2700W Form Rack and Tower Type Phase Single Phase Energy Saving Yes - ECO Mode Efficiency >94%...