Siemens MindConnect Nano Getting Started page 82

Getting connected to mindsphere
Hide thumbs Also See for MindConnect Nano:
Table of Contents

Advertisement

Appendix
A.2 Technical specifications of MindConnect Nano
EMC
Interference immunity on signal
cables >30m
Interference immunity on signal
cables < 30m
Interference immunity against voltage surge
asymmetric interference
symmetric interference
Interference immunity against high-frequency electromagnetic fields
Interference immunity against high
frequency radiation
Interference immunity to magnetic fields
Interference immunity to magnetic
fields at 50 Hz
Emission of conducted and non-conducted interference
Interference emission via line/AC
current cables
Degree and class of protection
IP (at the front)
IP (rear)
Standards, approvals, certificates
CE mark
UL approval
UL 508
cULus
RCM (formerly C-TICK)
KC approval
EMC
EN 61000-6-2
Dust protection
FCC
Marine approval
Germanischer Lloyd (GL)
American Bureau of Shipping
(ABS)
Bureau Veritas (BV)
82
±2 kV acc. to IEC 61000-4-5, surge, length > 30 m;
·
±1 kV acc. to IEC 61000-4-4; burst; length < 3 m;
·
±2 kV acc. to IEC 61000-4-4; burst; length > 3 m;
·
±2 kV acc. to IEC 61000-4-5, surge asymmetric
±1 kV acc. to IEC 61000-4-5, surge symmetric
10 V/m for 80 - 1000 MHz and 1.4 - 2 GHz, 80% AM acc. to IEC 61000-4-3;
·
3 V/m for 2 - 2.7 GHz, 80% AM acc. to IEC 61000-4-3;
·
10 V/m for 10 kHz - 80 MHz, 80% AM acc. to IEC 61000-4-6
·
100 A/m; to IEC 61000-4-8
EN 61000-6-3, EN 61000-6-4, CISPR 22 Class B, FCC Class A
IP20
IP40
Yes
Yes
Yes
Yes
Yes
Yes
CE, EN 61000-6-4:2007, EN 61000-6-2:2005
Yes
Protection against foreign bodies > 1 mm
Yes
Yes
Yes
Yes
Getting Connected to MindSphere
Getting Started, 05/2018

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mindconnect iot2040

Table of Contents